TYPICAL CHIMNEY INSTALLATION
Section 4 - Chimney/Vent System
1. Chimney Cap
2. Double-Wall Chimney Pipe (36”)
3. Rubber Boot/Storm Collar Flashing
4. Roof-Support Bracket
5. Double-Wall Chimney Pipe (36”)
6. Finishing Collar
7. Slip Connector (14”)
8. Black (Single-Wall) Pipe (24”)
9. Black (Single-Wall) Tee
10. Barometric Damper
11. Black (Single-Wall) Pipe (12”)
12. Black (Single-Wall) Tee
13. Cleanout Cap
Minimize or eliminate horizontal runs and angle/elbow con-
nections, where possible. Consider chimney cleanout access
when installing. If your installation fails to achieve proper
draft, consider lengthening the vertical chimney.
Contact Lanair for Assistance with special circumstances.
Keep at least 3 ft. to barometric
damper from any fan, air source/
return, etc.
Vertical chimney must be a
minimum of 10 feet in length to
establish proper draft
Check local codes for exterior-
clearance guidelines
Must use Class-A double-wall
pipe for roof penetration,
exterior chimney ue, and near
combustable surfaces
Chimney cap must be
at least 3 ft. taller than
any object within 10 ft.