Landis+Gyr Appendix C - Bench Testing
Series IV Concentrator U and I Guide 98-1031 Rev AA 85
Verification
To verify the operational condition of the concentrator:
1. Connect the Console port DB9 connector of the Console/LAN Packet Protocol cable (PN 19-
1126) to the COM port of a laptop or a PC.
2. Configure the port for the following:
• 9600 baud
• 8 bits
• No parity
• 1 Stop bit
• No flow control
Check the concentrator via the console menu interface. There are three components:
• WAN Health Check
• CPU and Configuration Check
• LAN Health Check
WAN Health Check
The WAN health is determined based on the TIME exchange between the CPU and the Gridstream
WAN Radio. WAN conditions and their interpretation are provided below.
Ideal WAN
Figure C.3 shows output under ideal conditions. This scenario indicates that the CPU to Gridstream
Radio serial communication and the Gridstream network is operational.
Figure C.3 Boot up WAN