Micro125 User Guide Part Number 900-588 Revision B March 2013
Copyright and Trademark © 2013 Lantronix, Inc. All rights reserved. No part of the contents of this book may be transmitted or reproduced in any form or by any means without the written permission of Lantronix, Inc. Lantronix® and DeviceLinx® are registered trademarks of Lantronix, Inc. DeviceInstaller™ is a trademark of Lantronix, Inc. Windows® and Internet Explorer® are registered trademarks of Microsoft Corporation Mozilla® and Firefox® are registered trademarks of the Mozilla Foundation.
Table of Contents Copyright and Trademark ______________________________________________ Warranty ___________________________________________________________ Contacts ___________________________________________________________ Disclaimer __________________________________________________________ Revision History _____________________________________________________ List of Figures _______________________________________________________ List of Tables _______________________________________________________
Host List Configuration _______________________________________________ Retry Settings___________________________________________________ Host Information _________________________________________________ Channel 1 and Channel 2 Configuration _________________________________ Serial Settings __________________________________________________ Connection Settings - TCP ________________________________________ Connection Settings - UDP ________________________________________ Apply Settings ___________________
Send Characters ________________________________________________ DisConnTime (Inactivity Timeout) ______________________________________ Send Characters ____________________________________________________ Telnet Terminal Type ________________________________________________ Channel (Port) Password _____________________________________________ 9.
A: Binary to Hexadecimal Conversions 73 Converting Binary to Hexadecimal ______________________________________ 73 Conversion Table ________________________________________________ 73 Scientific Calculator ______________________________________________ 74 List of Figures Figure 3-1. Evaluation Board Connected to Serial Device and Network ____________ Figure 5-1. Web-Manager Login Window ____________________________________ Figure 5-2.
1. Using This Guide Purpose and Audience This guide covers the DeviceLinx Micro125 embedded device server. It provides the information needed to configure, use, and update the Micro125 firmware and is intended for OEMs and system integrators who are embedding Micro125 in their end product designs. Chapter Summary The remaining chapters in this guide include: Chapter Description 2: Introduction Describes the main features of the Micro125 and the protocols it supports.
1: Using This Guide Additional Documentation Visit the Lantronix Web site at www.lantronix.com/support/documentation for the latest documentation and the following additional documentation. Document Description Micro125 Integration Guide Provides information about the Micro125 hardware, testing the Micro125 using the evaluation board, and integrating the Micro125 into your product. Provides information on using the Windows-based utility to create a virtual com port.
2. Introduction This chapter summarizes the Micro125 device server’s features and the basic information needed to get started. Capabilities The Micro125 device server has the following capabilities: Connects devices through a TCP data channel or through a Telnet connection to computers or to another device server. The Micro125 also supports UDP datagrams. Contains a web [HTTP] server allowing presentation of custom content and easy configuration through a browser.
2: Introduction Protocol Support The Micro125 device server uses the Internet Protocol (IP) for network communications. It uses the Transmission Control Protocol (TCP) to assure that no data is lost or duplicated, and that everything sent to the connection arrives correctly at the target. Supported protocols include: ARP, UDP, TCP, ICMP, Telnet, TFTP, AutoIP, DHCP, HTTP, and SNMP for network communications and management. TCP, UDP, and Telnet for connections to the serial port.
2: Introduction IP Address Every device connected to an IP network must have a unique IP address. This address is used to reference the specific unit. The Micro125 is automatically assigned an IP address on DHCP-enabled networks, as it is DHCP-enabled by default. Port Numbers Every TCP connection and every UDP datagram is defined by a destination IP address and a port number. For example, a Telnet application commonly uses port number 23. A port number is similar to an extension on a phone system.
3. Getting Started This chapter covers the steps required to get an embedded device physically connected. Physically Connecting the Unit The following diagram shows a properly installed Micro125. Other devices connect in a similar manner. Figure 3-1. Evaluation Board Connected to Serial Device and Network 10/100 Ethernet CON2 J1 +5 RS232 1. Connect a computer or serial device to your unit. 2. Connect an Ethernet cable to the RJ-45 Ethernet port. 3.
3: Getting Started IP Address Your device server must have a unique IP address on your network. The systems administrator generally provides the IP address and corresponding subnet mask and gateway. The IP address must be within a valid range, unique to your network, and in the same subnet as your PC.
4. Using DeviceInstaller This chapter covers the steps for getting the Micro125 device server online and viewing its current configuration. Note: DeviceInstaller is a free utility program provided by Lantronix that discovers, configures, upgrades, and manages Lantronix Device Servers. It can be downloaded from the Lantronix website at www.lantronix.com/support/downloads.
4: Using DeviceInstaller 4. Select Assign a specific IP address and click Next. 5. Enter the IP address. The Subnet mask displays automatically based on the IP address; if desired, you may change it. On a local network, you can leave the Default gateway blank (all zeros). Click Next. 6. Click the Assign button and wait several seconds until a confirmation message displays. Click Finish. 7. Select the device from the main window list and select Ping from the Tools menu.
4: Using DeviceInstaller Device Details Settings Description Comments Configurable field. Information about the Micro125. Double-click the field, type in the value, and press Enter to complete. This description or comment is not visible on other PCs or laptops using DeviceInstaller. Device Family Non-configurable field. Displays the Micro125’s device family as Micro125. Type Non-configurable field. Displays the device type as Micro125. ID Non-configurable field.
4: Using DeviceInstaller Device Details Settings Description Firmware Upgradeable Non-configurable field. Displays True, indicating the Micro125’s firmware is upgradeable as newer versions become available. Supports Configurable Pins Non-configurable field. Displays False, indicating configurable pins are not available on the Micro125. Supports Email Triggers Non-configurable field. Displays False, indicating email triggers are not available on the Micro125.
5. Configuration Using Web Manager You must configure the unit so that it can communicate on a network with your serial device. For example, you must set the way the unit will respond to serial and network traffic, how it will handle serial packets, and when to start or close a connection. The unit’s configuration is stored in nonvolatile memory and is retained without power. You can change the configuration at any time. The unit performs a reset after you change and store the configuration.
5: Configuration Using Web Manager Figure 5-1. Web-Manager Login Window 7. Perform one of the following: If no Telnet/Web Manager password has been defined (default), leave both fields blank and click OK. If a Telnet/Web Manager password has been defined, leave the username blank, type in the password, and then click OK. The Web-Manager displays. Figure 5-2. Lantronix Web-Manager The main menu is in the left pane of the Web-Manager window.
5: Configuration Using Web Manager Network Configuration The unit’s network values display when you select Network from the main menu. The following sections describe the configurable parameters on the Network Settings page. Figure 5-3. Network Settings Network Mode 1. Click Network from the main menu. 2. Select Wired Only. It is the only choice for Network Mode as it enables the Ethernet network connectivity. Automatic IP Address Configuration An IP address can be assigned automatically.
5: Configuration Using Web Manager 3. Enter the following (as necessary): Dynamic IP Setting Description BOOTP Select Enable to permit the Bootstrap Protocol (BOOTP). server to assign the IP address from a pool of addresses automatically. Enable is the default. DHCP Select Enable to permit the Dynamic Host Configuration Protocol (DHCP) to assign a leased IP address to the Micro125 unit automatically. Enable is the default. AutoIP Select Enable to permit the Micro125 to generate an IP in the 169.254.
5: Configuration Using Web Manager Ethernet Configuration You must specify the speed and direction of data transmission. To specify how data will be transmitted: 1. On the main menu, click Network. 2. Enter the following (as necessary): Ethernet Settings Description Auto Negotiate With this option, the Ethernet port auto-negotiates the speed and duplex with the hardware endpoint to which it is connected. This is the default.
5: Configuration Using Web Manager Server Configuration The unit’s server values display when you select Server from the main menu. The following sections describe the configurable parameters on the Server Settings page. Figure 5-4. Server Settings To configure the Micro125’s device server settings: 1. On the main menu, click Server. 2.
5: Configuration Using Web Manager Advanced Advanced Settings Description ARP Cache Timeout (secs) When the unit communicates with another device on the network, it adds an entry into its ARP table. ARP Cache timeout defines the number of seconds (1-600) before it refreshes this table. TCP Keepalive (secs) TCP Keepalive time defines how many seconds the unit waits during an inactive connection before checking its status. If the unit does not receive a response, it drops that connection.
5: Configuration Using Web Manager Figure 5-5. Hostlist Settings 2. Enter or modify the following fields: Retry Settings Retry Settings Description Retry Counter Enter the value for the number of times the Micro125 should attempt to retry connecting to the host list. Retry Timeout Enter the duration (in milliseconds) the Micro125 should abandon attempting a connection to the host list. Host Information Host Information Settings Description Host Address Enter or modify the host’s IP address.
5: Configuration Using Web Manager Serial Settings To configure the channel’s serial settings: 1. On the main menu, click Serial Settings (under Channel 1 or Channel 2) to display the Serial Settings window. Figure 5-6. Channel Serial Settings 2. In the available fields, enter the following information: Channel 1 or Channel 2 Channel Setting Description Disable Serial Port Available on Channel 1 settings only. When selected, disables communication through the serial port.
5: Configuration Using Web Manager Port Settings Description Flow Control Flow control manages data flow between devices in a network to ensure it is processed efficiently. Too much data arriving before a device is prepared to manage it causes lost or retransmitted data. None is the default. Baud Rate The unit and attached serial device, such as a modem, must agree on a speed or baud rate to use for the serial connection.
5: Configuration Using Web Manager Flush Input Buffer (Serial to Network) Flush Input Buffer Settings Description With Active Connect Select Yes to clear the input buffer with a connection that is initiated from the device to the network. The default is No. With Passive Connect Select Yes to clear the input buffer with a connection initiated from the network to the device. The default is No.
5: Configuration Using Web Manager Connection Settings - TCP To configure a channel’s TCP settings: 1. On the main menu, click Connection. The Connection Settings window for the channel displays. Figure 5-7.
5: Configuration Using Web Manager 2. In the available fields, enter or modify the following information: Connect Protocol Connect Protocol Setting Description Protocol From the drop-down menu, select TCP. Connect Mode: Passive Connection Passive Connection Mode Settings Description Accept Incoming Select Yes to accept incoming connections. The default is Yes. Password Required Determines whether a password is required for an incoming passive connection.
5: Configuration Using Web Manager Endpoint Configuration Endpoint Configuration Settings Description Local Port Enter the local port number. Auto increment for active connect Select to auto-increment the local port number for new outgoing connections. The range of auto-incremented port numbers is 50,000 to 59,999 and loops back to the beginning when the maximum range is reached. Remote Port Enter the remote port number. Remote Host Enter the IP address of the remote device.
5: Configuration Using Web Manager Disconnect Mode Settings Description Check EOT (Ctrl-D) Select Yes to drop the connection when Ctrl-D or Hex 04 is detected. Both Telnet Com Port Cntrl and Check EOT (Ctrl+ D) must be enabled for Disconnect with EOT to function properly. Ctrl+D is only detected going from the serial port to the network. The default setting is No. Inactivity Timeout Use this parameter to set an inactivity timeout.
5: Configuration Using Web Manager Connect Protocol Connection Protocol Description Protocol Select UDP from the drop-down menu. Datagram Mode Datagram Mode Settings Description Datagram Type Configures the remote IP or network broadcast address and the remote port. Enter 01 for directed or broadcast UDP. The default setting is 00. Accept Incoming Select Yes to accept incoming UDP datagrams.
5: Configuration Using Web Manager Figure 5-9. Applying Settings Apply Defaults 1. Click the Apply Factory Defaults button to set the device server back to the default settings. For details see Default Settings on page 61. 2. Click Yes to set factory settings, or click No to cancel. Figure 5-10.
6. Configuration via Telnet or Serial Port (Setup Mode) You must configure the unit so that it can communicate on a network with your serial device. As an alternative to using a web browser, as described in the previous chapter, you can use the following procedures remotely or locally: Use a Telnet connection to configure the unit over the network. Use a terminal or terminal emulation program to access the serial port locally.
6: Configuration via Telnet or Serial Port (Setup Mode) To establish a Telnet connection: 1. From the Windows Start menu, click Run and type the following command, where x.x.x.x is the IP address, and 9999 is the unit’s fixed network configuration port number: Windows: telnet x.x.x.x 9999 UNIX: telnet x.x.x.x:9999 2. Click OK. The following information displays. Figure 6-1. MAC Address MAC address 00204AAE0412 Software version V6.8.0.4 (121207) M125 AES library version 1.8.2.
6: Configuration via Telnet or Serial Port (Setup Mode) Note: The easiest way to enter Setup Mode is to hold down the x key at the terminal (or emulation) while resetting the unit. You must do this within three seconds of resetting the Micro125. At this point, the screen display is the same as when you use a Telnet connection. To continue, go to step 4, above under the section, Telnet Connection .
7. Setup Mode: Server Configuration This chapter explains how to configure the network settings. Note: Current values appear in parentheses. Server Configuration (Option 0) The unit’s basic network parameters display when you select Server configuration (option 0). The IP Address, Set Gateway IP Address, and Netmask fields display the current values. IP Address : (000) .(000) .(000) .
7: Setup Mode: Server Configuration Set Gateway IP Address The gateway address, or router, allows communication to other LAN segments. The gateway address should be the IP address of the router connected to the same LAN segment as the unit. The gateway address must be within the local network. The default is N (No), meaning the gateway address has not been set. To set the gateway address, type Y and enter the address.
7: Setup Mode: Server Configuration Change Telnet/Web-Manager Password Setting the Telnet/Web-Manager password prevents unauthorized access to the setup menu through a Telnet connection to port 9999 or through web pages. The password must have 4 characters. Change Telnet/Web-Manager password (N) ? _ An enhanced password setting (for Telnet access only) of 16 characters is available under Security Settings (Option 6) on page 58.
8. Setup Mode: Channel Configuration This chapter explains how to configure the serial port. Two channels may be configured in Micro125: Channel 1 and Channel 2. Note: The directions for configuring Channel 1 provided below may also be used for Channel 2. Channels Select Channel 1 (option 1) from the Change Setup menu to define how the serial port responds to network and serial communications. The following sections describe the configurable parameters within the Channel configuration menu. Figure 8-1.
8: Setup Mode: Channel Configuration I/F (Interface) Mode The Interface (I/F) Mode is a bit-coded byte entered in hexadecimal notation. I/F Mode (4C) ? _ The following table displays available I/F Mode options: Note: All bit positions in the table that are blank represent “don’t care” bits for that particular option, which can be set to either a 0 or 1 value. Table 8-1.
8: Setup Mode: Channel Configuration Table 8-3. Interface Mode Options I/F Mode Option 7 6 5 4 3 2 1 0 RS-422 4-wire 0 1 RS-485 2-wire 1 1 Flow Flow control sets the local handshaking method for stopping serial input/output. Flow (00) ? _ Use the following table to select flow control options: Table 8-4.
8: Setup Mode: Channel Configuration Connect Mode Connect Mode defines how the unit makes a connection, and how it reacts to incoming connections over the network. ConnectMode (C0) ? _ Enter Connect Mode options in hexadecimal notation. Note: All bit positions in the table that are blank represent “don’t care” bits, for that particular option, which can be set to either a 0 or 1 value. Table 8-6.
8: Setup Mode: Channel Configuration Connect Mode Option 7 Modem Response Only (Verbose) 6 5 4 3 2 1 0 0 0 1 1 1 0 a) Incoming Connection Incoming Connection Mode Description Never Accept Incoming Rejects all external connection attempts. Accept with active Modem Control In Accepts external connection requests only when the Modem Control In input is asserted. Cannot be used with Modem Mode. Always Accept Accepts any incoming connection when a connection is not already established.
8: Setup Mode: Channel Configuration Active Startup Mode Description If present, the port number must follow the IP address, must be presented as a decimal number in the range 1-65535, and must be preceded by a forward slash (ASCII 0x2F). The slash separates the IP address and the port number. If you omit the port number from a command string, the internally stored remote port number starts a connection.
8: Setup Mode: Channel Configuration Figure 8-2. Hostlist Option Baudrate (9600) ? I/F Mode (4C) ? Flow (00) ? Port No (10001) ? ConnectMode (25) ? Send '+++' in Modem Mode (Y) ? Auto increment source port (N) ? Hostlist : 01. IP : 172.019.000.001 02. IP : 172.019.000.002 03. IP : 172.019.000.003 Port : 00023 Port : 03001 Port : 10001 Change Hostlist ? (N) ? Y 01. IP address : (172) .(019) .(000) .(001) 02. IP address : (172) .(019) .(000) .(002) 03. IP address : (172) .(019) .(000) .(003) 04.
8: Setup Mode: Channel Configuration d) Datagram Type Datagram Type Description Directed UDP When selecting this option, you are prompted for the Datagram type. Enter 01 for directed or broadcast UDP. Datagrams of type 01 can be sent as a broadcast by enabling the Send as Broadcast option. The default is not to broadcast. When the UDP option is in effect, the unit never attempts to initiate a TCP connection because it uses UDP datagrams to send and receive data.
8: Setup Mode: Channel Configuration Table 8-9. Modem Mode Messages Message Meaning Full Verbose OK Command was executed without error. CONNECT A network connection has been established. NO CARRIER A network connection has been closed. RING n.n.n.n. A remote device, having IP address n.n.n.n, is connecting to this device.
8: Setup Mode: Channel Configuration If this sequence is not followed, the unit remains in data transfer mode. Table 8-10. Modem Mode Commands Modem Mode Command Function ATDTx.x.x.x,pppp, ATDTx.x.x.x/pppp, or ATDTx.x.x.x:pppp Makes a connection to an IP address (x.x.x.x) and a remote port number (pppp). ATDTx.x.x.x Makes a connection to an IP address (x.x.x.x) and the remote port number defined within the unit. ATD0.0.0.
8: Setup Mode: Channel Configuration Show IP addr after 'RING' Show IP addr after ‘RING’ (Y) ? Disable or enable the Micro125's ability to show the IP address after RING in Modem Mode. The default is Y (Yes), to show the IP address. Auto Increment Source Port Auto increment source port (N) ? _ Y (Yes) auto increment the source port. The Micro125 increments the port number used with each new connection. Remote IP Address This is the destination IP address used with an outgoing connection.
8: Setup Mode: Channel Configuration Table 8-11. Disconnect Mode Options Disconnect Mode Option 7 Disconnect when Modem Control In is not asserted Ignore Modem Control In Hard disconnect 6 5 4 3 2 1 0 1 0 Telnet Com Port Cntrl and terminal type setup Channel (port) password (6) (1) 1 (2) 1 (3) 0 Disable hard disconnect 1 State LED off with connection Disconnect with EOT (^D) (5) (4) 1 1 (1) The Telnet Com Port Control feature is used in conjunction with Com Port Redirector.
8: Setup Mode: Channel Configuration Flush Mode (Buffer Flushing) Using this parameter, you can control line handling and network buffers with connection startup and disconnect. FlushMode (00) ? _ You can also select between two different packing algorithms. Note: All bit positions in the table that are blank represent “don’t care” bits, for that particular option, which can be set to either a 0 or 1 value. Table 8-12.
8: Setup Mode: Channel Configuration Option 7 6 5 4 3 2 1 0 Interval: 12ms 0 0 Interval: 52ms 0 1 Interval: 250ms 1 0 Interval: 5sec 1 1 Trailing Characters None 0 0 One 0 1 Two 1 0 Send Characters 2-Byte Send Character Sequence Send Immediately After Send chars 1 1 Packing Interval Packing Interval defines how long the unit should wait before sending accumulated characters. This wait period is between successive network segments containing data.
8: Setup Mode: Channel Configuration DisConnTime (00:00) ?: To disable the inactivity timeout, enter 00:00. Range is 0 (disabled) to 5999 seconds (99 minutes, 59 seconds). Default is 0. Send Characters Enter up to two characters in hexadecimal representation in sendchar. SendChar 1 (00) ? _ SendChar 2 (00) ? _ If the unit receives a character on the serial line that matches one of these characters, it sends the character immediately, along with any awaiting characters, to the TCP connection.
9. Setup Mode: Advanced Settings Expert Settings (Option 5) Note: You can change the Enable alternate MAC setting using telnet or serial connections only. It is not available through the Web-Manager. CAUTION: Only an expert should change these parameters. You must definitely know the consequences the changes might have. Figure 9-1.
9: Setup Mode: Advanced Settings ARP Cache Timeout in Seconds Whenever the unit communicates with another device on the network, it adds an entry into its ARP table. The ARP Cache timeout option allows you to define how many seconds (1-600) the unit will wait before timing out this table. ARP Cache timeout in s (1s - 600s) : (600) ? Disable Monitor Mode at Bootup This option allows you to disable all entries into Monitor Mode during startup, except for the ‘xxx’ sequence.
9: Setup Mode: Advanced Settings Security Settings (Option 6) Note: You can change security settings by means of Telnet or serial connections only, not on the Web-Manager. We recommend that you set security over the dedicated network or over the serial setup to prevent eavesdropping. CAUTION: Disabling both Telnet Setup and Port 77FE will prevent users from accessing the setup menu from the network. Disabling Port 77FE also disables the Web from configuring the device.
9: Setup Mode: Advanced Settings Disable TFTP Firmware Upgrade This setting defaults to the N (No) option. The Y (Yes) option disables the use of TFTP to perform network firmware upgrades. With this option, you can download firmware upgrades over the serial port using DeviceInstaller’s Recover Firmware procedure. (See 10: Firmware Upgrades.
9: Setup Mode: Advanced Settings To configure AES encryption on the Micro125: Enable Encryption (N) Y Key length in bits (0): 128 Change Keys (N) Y Enter Keys: **-**-**-**-**-**-**-**-**-**-**-**-**-**-**-**- 1. When prompted to enable encryption, select Y. 2. When prompted, enter the encryption key length. The Micro125 supports 128-, 192-, and 256-bit encryption key lengths. 3. When prompted to change keys, select Y. 4. At the Enter Keys prompt, enter your encryption key.
9: Setup Mode: Advanced Settings Default Settings (Option 7) Select 7 to reset the unit’s channel configuration and expert settings to the default settings. The server configuration settings for IP address, gateway IP address, and netmask remain unchanged.
9: Setup Mode: Advanced Settings Security Settings Defaults Security Setting Default Configuration Disable SNMP No SNMP community name public Disable Telnet setup No Disable TFTP Firmware Update No Disable Port 77FEh No Disable Web Server No Disable Web Setup No Disable ECHO ports Yes Enable Encryption No Enable Enhanced Password No Micro125 User Guide 62
10. Firmware Upgrades Obtaining Firmware You can obtain the most up-to-date firmware and release notes for the unit from the Lantronix web site (www.lantronix.com/support/downloads) or by using anonymous FTP (ftp.lantronix.com/pub). Reloading Firmware There are several ways to update the unit's internal operational code (*.ROM): using DeviceInstaller (the preferred way), using TFTP, or using the serial port. You can also update the unit's internal Web interface (*.COB) using TFTP or DeviceInstaller.
10: Firmware Upgrades Figure 10-1. TFTP Window 6. Click the Upload Now button to transfer the file to the unit. The unit performs a power reset after the firmware has been loaded and stored. Using TFTP: Command Line Interface To download new firmware from a computer: 1. Enter the following from a TFTP command line interface: tftp –i put The following examples demonstrate the TFTP command sequence to download the .rom file and the .
10: Firmware Upgrades Recovering the Firmware Using the Serial Port and DeviceInstaller If for some reason the firmware is damaged, you can recover the firmware file by using DeviceInstaller to download the *.ROM file over the serial port. To recover firmware: 1. Start DeviceInstaller. If your PC has more than one network adapter, a message displays. Select an adapter and click OK. 2. From the Tools menu, select Advanced/Recover Firmware. The Serial Port Firmware Upgrade window displays. 3.
11. Monitor Mode Monitor Mode is a command-line interface used for diagnostic purposes. There are two ways to enter Monitor Mode: locally using the serial port or remotely using the network. Entering Monitor Mode Using the Serial Port To enter Monitor Mode locally: 1. Follow the same steps used for setting the serial configuration parameters (see Serial Port on page 36). 2. Instead of typing three x keys, however: 3. Type zzz (or xx1) to enter Monitor Mode with network connections. 4.
11: Monitor Mode Table 11-1. Monitor Mode Commands Command Command Name Function VS x.x.x.x Version Queries software header record (16 bytes) of unit with IP address x.x.x.x. GC x.x.x.x Get Configuration Gets configuration of unit with IP address x.x.x.x as hex records (120 bytes). SC x.x.x.x Send Configuration Sets configuration of unit with IP address x.x.x.x from hex records. PI x.x.x.x Ping Pings unit with IP address x.x.x.x to check device status.
11: Monitor Mode Note: Entering any of the commands listed above generates one of the following command response codes: Table 11-2.
12. Troubleshooting This chapter discusses how you can diagnose and fix errors quickly without having to contact a dealer or Lantronix. It helps to connect a terminal to the serial port while diagnosing an error to view summary messages that may display. When troubleshooting, always ensure that the physical connections (power cable, network cable, and serial cable) are secure. Note: Some unexplained errors might be caused by duplicate IP addresses on the network.
12: Troubleshooting Problem/Message When you try to assign an IP with DeviceInstaller, you get the following : "No response from device! Verify the IP, Hardware Address and Network Class. Please try again." Reason Solution The device server may not be plugged into the network properly. Make sure that the Link LED is lit. If the Link LED is not lit, then the device server is not properly plugged into the network.
12: Troubleshooting Problem/Message Reason Solution The device server appears to be set up correctly, but you are not communicating with your device attached to the device server across the network. If you are sure that the serial port setting is correct, then you may not be connecting to the correct socket of the device server. You can check to see whether there is a socket connection to or from the device server by looking at the Status LED.
12: Troubleshooting Technical Support If you are experiencing an error that is not described in this chapter, or if you are unable to fix the error, you have the following options: Technical Support US Check our online knowledge base or send a question to Technical Support at http://www.lantronix.com/support. Phone: (800) 422-7044 (US Only) (949) 453-7198 Technical Support Europe, Middle East, and Africa Phone: +33 (0)1 39 30 41 72 +49 (0) 180 500 13 53 (Germany Only) Email: eu_techsupp@lantronix.
A: Binary to Hexadecimal Conversions Many of the unit’s configuration procedures require assembling a series of options (represented as bits) into a complete command (represented as a byte). Convert the resulting binary value to a hexadecimal representation. Converting Binary to Hexadecimal Following are two simple ways to convert binary numbers to hexadecimals. Conversion Table Hexadecimal digits have values ranging from 0 to F, which are represented as 0-9, A (for 10), B (for 11), etc.
A: Binary to Hexadecimal Conversions Scientific Calculator Another simple way to convert binary to hexadecimals is to use a scientific calculator, such as the one available on Windows’ operating systems. For example: 1. On the Windows’ Start menu, click ProgramsAccessoriesCalculator. 2. On the View menu, select Scientific. The scientific calculator displays. 3. Select Bin (Binary), and type the number to convert. 4. Click Hex. The hexadecimal value displays.