User Manual

Configure
3.6.5 Connect Mode
Connect Mode defines how the unit makes a connection, and how it reacts to incoming
connections over the network. Enter Connect Mode options in hexadecimal notation.
Note: See Table 35 - Binary to Hexadecimal Conversion Table.
Table 9 - Connect Mode Options
Connect Mode Option 7 6 5 4 3 2 1 0
Incoming Connection
Never accept incoming 0 0 0
Accept incoming with DTR 0 1 0
Accept unconditional 1 1 0
Response
Nothing (quiet) 0
Character response (C=connect,
D=disconnect, N=unreachable)
1
Startup
No active startup 0 0 0 0
With any character 0 0 0 1
With active DTR
(1)
0 0 1 0
With CR (0x0D) only 0 0 1 1
Manual connection 0 1 0 0
Autostart 0 1 0 1
Datagram Type
Directed UDP 1 1 0 0
Modem Mode
Full Verbose 1 0 1 1 0
Without Echo 0 0 1 1 0
1-character Response 1 0 1 1 1
Manual Connection: When you use manual connection, you are not required to enter the
entire IP address if the IP is already configured as the remote IP address in the unit. For
example, if the remote IP address already configured in the unit is 129.1.2.3, then an example
command string would be C3/7. (This would connect to 129.1.2.3 and port 7.) You may also
use a different ending for the connection string. For example, C50.1/23 would connect you to
129.1.50.1 and port 23.
UDS-10 User Guide 3-17