Data Sheet

DATA SHEET
0010000
ÖLFLEX
®
CLASSIC 100
valid from :
19.05.2010
Originator: H. Krämer / PDC
approved: H. Pfeffer / PDC
Document: DB0010000EN page 1 of 1
Nr.: 0019/0894
Application
ÖLFLEX
CLASSIC 100 cables are connecting- and control cables for flexible use and fixed installation for
medium mechanical use. They are for use in dry, damp and wet rooms. They may only be installed outdoors with
UV-protection and in observation of the temperature range. At room temperature they are generally resistant
against acids, caustics solutions and certain oils. ÖLFLEX
CLASSIC 100 cables are used as supply and flexible
connecting cable in machine tool manufacture, plant engineering, in power stations, in heating and air
conditioning installations, etc. Suitable for freely moved without forced guidance and tensile stress.
Technical data
Conductor bare copper, fine wire strand in accordance to IEC 60228
resp. VDE 0295, Class 5
Design in accordance to HD 21.13S1 that is VDE 0281-13
Core insulation LAPP special PVC-compound P 8/1, better than the PVC compound TI2 in
accordance to VDE 0207 part 4
Identification with up to 5 cores are coloured-coded in acc. to HD 186 resp. VDE 0293
or HD308S2 that is VDE 0293-308; cables with more than 5 cores are colour-coded in
acc. to LAPP-ÖLFLEX colour-code.
Outer sheath PVC-compound TM2 in acc. to VDE 0207 part 5 with increased requests
to LAPP specification
Nominal voltage 0,5 mm
2
to 1,5 mm
2
: 300 / 500 V
from 2,5 mm
2
: 450 / 750 V
from 2,5 mm
2
, fixed and protected installation: 600 / 1000 V
Test voltage 4000 V AC
Temp. range for flexible use -5 up to +70° C max. conductor temperature
fixed installation -40 up to +80° C max. conductor temperature
Min. bending radius flex. use : 15 x cable diameter
fixed installation: 4 x cable diameter
Flame retardant in acc. to IEC 60332-1-2 resp. VDE 0482-332-2-1
Tests in acc. to IEC 60811 resp. VDE 0473 and VDE 0472
EC directive This cable is conform to ECD 2006/95/EC (Low Voltage Directive).

Summary of content (1 pages)