Datasheet

U.I. Lapp
GmbH
DATA SHEET
ÖLFLEX
®
CLASSIC FD 810
DB 0026100
valid from: 22.09.2015
Originator: KASC / PDC
approved: HAPF / PDC
Document: DB0026100EN
All rights reserved acc. to DIN ISO 16016.
PD 0019/2.2_11.10EN
Application
ÖLFLEX
CLASSIC FD 810 cables are high flexible, power and control cables with sheath of PVC for flexible use and fixed
installation under normal mechanical load conditions. They are designed for use in dry, damp or wet rooms. They may only
be installed outdoors with UV-protection and considering the temperature range. The cables are generally resistant against
acids, caustics solution and specific oils. Usage on motor drum guidance or under a strain of more than 15 N/mm
2
is not
allowed.
Application range:
In power chain or moving machine parts; suitable for use in measuring, control and regulating circuits; power circuits for
electrical equipment used in automation engineering; assembly lines, production lines in all kinds of machines; plant engi-
neering
Design
Design based on
EN 50525-2-51 resp. VDE 0285-525-2-51
Conductor fine wire strands of bare copper acc. to IEC 60228 that is VDE 0295, class 6
Core insulation LAPP special PVC compound P8/1 with increased requests to Lapp specifification
TI2, acc. to EN 50363-3 resp. VDE 0207-363-3
Core identification acc. to VDE 0293-1, with or without GN / YE ground conductor,
black cores with white numbers acc. to EN 50334 resp. VDE 0293-334
Outer sheath PVC-compound TM2 acc. to EN 50363-4-1 resp. VDE 0207-363-4-1
with increased requests to LAPP specification
colour: silver grey, similar RAL 7001
Electrical properties
Nominal voltage U
0
/U: 300/500 V
Test voltage Core / Core: 4000 V
Mechanical and thermal properties
Min. bending radius occasional flexing: 7,5 x outer diameter
fixed installation: 4 x outer diameter
Number of bending/ unbending
cycles 5 mio. cycles
Travel distance 10 m
Temperature range occasional flexing: 0 °C up to +70 °max. conductor temp.
fixed installation: -40 °C up to +70 °C max. conductor temp.
Flame retardant acc. to IEC 60332-1-2 resp. VDE 0482-332-1-2
Tests acc. to IEC 60811, EN 50395, EN 50396
EC-Directives These cables are conform to the EU-Directives 2014/35/EU (Low Voltage Directive)
and 2011/65/EU (RoHS, Restriction of the use of certain hazardous substances).