Data Sheet

U.I. Lapp
GmbH
DATA SHEET
ÖLFLEX
®
FD 90
DB 0026600
valid from: 2014-02-21
Originator: KASC / PDC
approved: HAPF / PDC
Document: DB0026600EN
All rights reserved acc. to DIN ISO 16016.
PD 0019/2.2_11.10EN
Application
ÖLFLEX
®
FD 90 are high-flexible sheathed cables designed for the European, North American and Canadian market, for
flexible use and fixed installation, under light and medium mechanical load conditions. The PVC sheath is increased oil re-
sistant. They are among others designed for use in dry and humid rooms. Considering the temperature range an outdoor use
is possible. In USA and Canada an outdoor use is not allowed. Usage of these cables in moving cable carriers or on motor
drum guidance or under a tensile strain of more than 15 N/mm² is not allowed.
Application range:
In machine tools or for internal wiring in industrial machines etc.
USE acc. to UL: PVC sheathed cable for external wiring or internal wiring of electric and electronic equipment.
USE acc. to CSA: Cables for internal wiring or external wiring with or without mechanical stresses.
Design
Approvals UL AWM Style 10107 (File No. E63634)
150 mm² cUL AWM I A/B, II A/B
120 mm² CSA AWM I A/B, II A/B, FT1
Design based on VDE 0250
Conductor extra fine wire strands of bare copper, acc. to IEC 60228 resp. VDE 0295, min. Class 6
Core insulation PVC compound (UL/CSA 90°C rating)
Core identification BK or GN/YE
Sheath PVC compound (UL/CSA 90°C rating); colour: Black, similar RAL 9005
Electrical properties at 20 °C
Nominal voltage U
0
/U IEC 600 / 1000 V
UL/CSA 600 V
Test voltage 4000 V AC
Specific insulation resistance > 20 G Ω x cm
Mechanical and thermal properties
Min. bending radius flexing: 7,5 x cable diameter
fixed installation: 3 x cable diameter
Number of bending/unbending
cycles 5 mio. cycles
Travel distance 10 m
Temperature range flexing: -5 °C up to +90 °C (UL/CSA) max. conductor temp.
fixed installation: -40 °C up to +90 °C (UL/CSA) max. conductor temp.
Oil resistance acc. to IEC 60811 bzw. VDE 0473-811 (90 °C, 7d)
80°C rating acc. to UL 758; CSA C22.2 No.210-05
Flammability flame retardant in acc. with IEC 60332-1-2 resp. VDE 0482-332-1-2
UL: Vertical flame test VW-1
CSA: FT1; FT2
Tests acc. to IEC 60811 resp. VDE 0473-811 and VDE 0472, EN 50395, EN 50396
EC Directives These cables are conform to the EC-Directives
2006/95/EC (Low Voltage Directive) and 2011/65/EU (RoHS, Restriction of the
use of certain hazardous substances).