Data Sheet

DATA SHEET
0035101
UNITRONIC
®
LiYY (TP)
valid from :
04.09.2006
elaborated by:
TE-K: M. Herb
Document: DB0035101_2EN page 1 of 1
Nr.: 0019/0894
Application
UNITRONIC
LiYY (TP) is a flexible, paired cable for control and data transmissions for fixed installation and
flexible use, but not for high flexible use in power chains and permanent moved applications. By the pair twisting
the electric circuits are well decoupled. UNITRONIC
LiYY (TP) is intended for use in dry and damp interiors, but
not outside. At room temperature they are generally resistant against acids, caustics solutions and certain oils.
Design and electrical characteristics in acc. to VDE 0812.
Design
Conductor in acc. to VDE 0812, but not tinned
up to 0,5 mm² in acc. to VDE 0295, class 5
Insulation PVC compound YI2 in acc. to VDE 0207 part 4
Coding according to DIN 47100
Stranding cores twisted into pairs, pairs twisted in layers
Sheath PVC compound YM2 in acc. to VDE 0207 part 5
Colour sheath grey
Technical Data
Conductor Loop resistance
cross section
[max./km]
[mm²]
0,14 148
0,25 79,9
up to 0,5 In acc. to VDE 0295
Specific insulation resistance in acc. to VDE 0207 part 4
min. Gxcm
10
Inductance mH/km
appr. 0.67
Operating Voltage for 0.14 mm² (not for power purposes) V
350
for 0,25 mm² (not for power purposes)
V
500
Test voltage for 0.14 mm² U
eff.
V
1200
for 0,25 mm²
U
eff.
V
1500
Minimum bending radius moved
10 x cable Ø
Temperature range moved °C
- 5 to + 70
static °C
- 40 to + 80
Flame propagation flame retardant to VDE 0482, part 265-2-1 / IEC 60 332-1

Summary of content (1 pages)