Datasheet
0046001
DATA SHEET
valid from:
05.08.2019
Creator: KASC / PDC
Released: ALTE / PDC
Document: DB0046001EN
Version: 06
Page 1 of 1
We reserve all rights according to DIN ISO 16016.
PD 0019/05_04.18EN
Application
d control cables at high ambient temperatures. The use of these
cables is recommended for example in the following fields:
Steel and iron works, cement and ceramic works, foundries, bakery equipment, electric motor industry, sauna and solarium construction,
thermal and heating elements, lighting technology, ventilator engineering, air conditioning technology, oven construction, galvanization
technology and polymer processing.
Design
Design
based on EN 50525-2-83 resp. VDE 0285-525-2-83
Conductor
fine wire strands of tinned copper acc. to IEC 60228 resp. VDE 0295, Class 5
Insulation
silicone compound EI2 acc. to VDE 0207-363-1
Core identification code
starting at 3 cores with GN/YE ground conductor
up to 5 cores coloured acc. to VDE 0293-308
starting at 6 cores: Black cores with white numbers
Stranding
cores are stranded in layers
7-core cables with 1+6 stranding
Outer sheath
silicone compound EM9 acc. to VDE 0207-363-2-1
Coral red like RAL 3016
dlsafjlöj f
Electrical properties at 20°C
Nominal voltage
300/500 V
Test voltage
core/core: 2000 V
Mechanical and thermal properties
Minimum bending radius
occasional flexing: 15 x cable Ø
fixed installation: 4 x cable Ø
Temperature range
occasional flexing: -25˚C bis +180˚C
(adequate ventilation provided)
fixed installation: -60˚C bis +180˚C
Flammability
flame retardant acc. to IEC 60332-1-2
Halogen free
acc. to IEC 60754-1
Corrosivity of gases
acc. to IEC 60754-2
Tests
acc. to IEC 60811, EN 50395, EN 50396
General requirements
These cables are conform to the EU-Directive 2014/35/EU (Low Voltage Directive)