Data Sheet

U.I. Lapp
GmbH
DAT
A SHEET
ÖLFLEX
®
CLASSIC 110 CH
DB 10035030
valid from: 2013-11-08
Originator: KASC / PDC
approved: HESC / PDC
Document: DB10035030EN Page 1 of 2
All rights reserved acc. to DIN ISO 16016.
PD 0019/2.2_11.10EN
Application
ÖLFLEX
®
CLASSIC 110 CH are screened, halogen free, oil resistant, highly flame retardant, power and control cables, de-
signed for the European and North American market, for occasional flexible use and fixed installation subject to normal
mechanical load conditions. They are among others for use in dry, damp and wet rooms. Considering the temperature range,
a temporary outdoor use is possible. Continuous busy movements, compulsory guidance respectively usage on cable drums
or pulleys or under a strain of more than 15 N / mis not allowed. ÖLFLEX
®
CLASSIC 110 CH cables are particularly used
in areas, where human and animal life as well as valuable property are exposed to high risk of fire hazards. In the event of a
fire minimal toxic and no corrosive gases occur. The screen is a protection against electrical interference.
Application range:
public buildings; airport, railway station; plant engineering, industrial machinery; heating and air conditioning systems, stage
applications; in EMC sensitive environments (electromagnetic compatibility)
USE according to UL: FRPE sheathed cable for internal wiring of appliances and external interconnection of electronic
equipment
Design
Design gem. UL AWM 758, Style 21089 and
acc. to EN 50525-3-11 resp. VDE 0285-525-3-11
Approval UL AWM 758, Style 21089 (File No. E63634)
Conductor fine wire strands of bare copper, acc. to IEC 60228 resp. VDE 0295, Class 5
Core insulation halogen free compound TI6, polyolefin based,
acc. to EN 50363-7 resp. VDE 0207-363-7, with increased requirements
Core identification acc. to VDE 0293-1, with or without GN/YE ground conductor
black cores with white numbers acc. to DIN EN 50334 resp. VDE 0293-334
Inner sheath halogen-free compound HM2, polyolefin based, acc. to DIN VDE 0250-214,
with increased requirements,
colour: silver grey, similar RAL 7001
Screen braid of tinned copper, coverage = 85% (nominal value)
Outer sheath halogen free compound HM2, polyolefin based, acc. to DIN VDE 0250-214,
with increased requirements,
LAPP LP Ultraflex FR
colour: silver grey, similar RAL 7001
Electrical properties
Nominal voltage VDE: U
0
/ U 300 / 500 V
UL: 600 V
Test voltage Core / Core 4000 V AC
Core / Screen 4000 V AC
Mechanical and thermal properties
Min. bending radius occasional flexing: 15 x outer diameter
fixed installation: 6 x outer diameter

Summary of content (2 pages)