Data Sheet

U.I. Lapp
GmbH
DATA SHEET
ÖLFLEX
®
CHAIN 809 CY
DB 1026751
valid from: 2014-02-21
Originator: KASC1 / PDC
Approved: HAPF / PDC
Dokument: DB1026751EN
All rights reserved acc. to DIN ISO 16016.
PD 0019/2.2_11.10EN
Temperature range fixed installation (VDE): -40 °C up to +70 °C max. conductor temp.
fixed installation(UL/CSA): -40 °C up to +80 °C max. conductor temp.
flexing (VDE): 0 °C up to +70 °C max. conductor temp.
flexing (UL/CSA): 0 °C up to +80 °C max. conductor temp.
Torsion movement in WTG TW-0 (5000 cycles at +5°C)
TW-1 (2000 cycles at ≥ -20°C)
± 150 °/m at 1 revolution per minute
Flammability flame retardant in acc. to IEC 60332-1-2 resp. VDE 0482-332-1-2
UL: Vertical flame test VW-1; CSA: FT1
Oil resistance TM54 acc. to DIN EN 50290-2-22
Tests acc. to IEC 60811 resp. VDE 0473 part 811, EN 50395, EN 50396
UL 1581 und CSA C22.2
EC directive This cable is conform to the EC-Directives 2006/95/EC (Low Voltage Directive)
and 2002/95/EC (RoHS, Restriction of the use of certain hazardous substances).