Data Sheet

U.I. Lapp
GmbH
DATA SHEET
ÖLFLEX® CLASSIC 100 yellow
DB 0010400
valid from: 15.11.2012
Originator: KASC / PDC
Approved: HAPF / PDC
Dokument: DB0010400EN Page 1 of 1
All rights reserved acc. to DIN ISO 16016.
PD 0019/2.2_11.10EN
Application
ÖLFLEX
CLASSIC 100 yellow cables are PVC connecting cables for flexible use and fixed installation for medium mechani-
cal use for special warning feature in accordance to VDE 0113 part 1 that is EN 60204 part 1. They are for use in dry, damp
or wet rooms. They may only be installed outdoors with UV-protection and in observation of the temperature range. At room
temperature they are generally resistant against acids, caustics solutions and certain oils. Suitable for freely moved without
forced guidance and tensile stress.
This cable is suitable for torsion application in wind turbines (WTG). The torsional load is limited to applications, as they
typically occur in the loop of a wind turbine.
Design
Design in accordance to HD 21.13S1 that is VDE 0281-13
Conductor bare copper, fine wire strand in accordance to IEC 60 228
that is VDE 0295, class 5
Core insulation LAPP special PVC-compound P 8/1, better than the PVC compound TI2 in
accordance to VDE 0207 part 4
Identification colored-coded in acc. to HD 186 resp. VDE 0293 or HD 308S2 that is
VDE 0293-308 with green/yellow ground conductor
Outer sheath PVC-compound TM2 in acc. to VDE 0207 part 5 with increased requests
to LAPP specification
Outer sheath color yellow (RAL 1016)
Electrical properties
Nominal voltage 450 / 750 V
Test voltage 4000 V AC
Mechanical and thermal properties
Min. bending radius occasional flexing: 15 x cable diameter
Fixed installation: 4 x cable diameter
Temperature range for flexible use -5 up to +70° C max. conductor temperature
fixed installation -30 up to +80° C max. conductor temperature
Torsion movement in WTG TW-0 (5000 cycles at ≥ +5°C)
TW-1 (2000 cycles at ≥ -20°C)
± 150 °/m at 1 revolution per minute
Flame retardant in acc. to IEC 60 332.1 resp. VDE 0482 part 265-2-1
Tests in acc. to VDE 0472 and IEC 811-x.x that is VDE 0473
EC-Directives This cable is conform to the EC-Directives 2006/95/EC (Low Voltage Directive) and
ECD 2002/95/EC (RoHS, Restriction of the use of certain hazardous substances).