Datasheet

1119752
DATA SHEET
valid from:
01.01.2019
Creator: HESC / PDC
Released: ALTE / PDC
Document: DB1119752EN
Version: 10
Page 1 of 1
We reserve all rights according to DIN ISO 16016.
PD 0019/05_04.18EN
Application
ÖLFLEX CLASSIC 110 cables are VDE approved power and control cables for occasional flexible use and fixed installation for medium
mechanical stresses. They are among others designed for use in dry, damp and wet conditions. If using outdoors, observe the indicated
temperature range and use with UV protection. They are largely resistant to acids, alkalis and certain oils at room temperature.
ÖLFLEX CLASSIC 110 cables are limited suitable for free and continuously recurring movements. The maximum tensile load is 15 N/mm²
of conductor cross-section during installation and operation. Compulsory guidance is not permitted.
Application range:
As power and connecting cable for control systems in machine tools, plant engineering and construction, industrial machnery, conveyor
systems, production and assembly lines as well as in measuring and control technology and data processing systems.
This cable is suitable for torsion application in wind turbines (WTG). The torsional load is limited to applications, as they typically occur in the
loop of a wind turbine.
Design
Design
Certification
Conductor
Insulation
Core identification code
Stranding
Outer sheath
dlsafjlöj f
Electrical properties at 20°C
Rated voltage
U₀ / U: 300 / 500 V
Test voltage
core / core: 4000 V AC
Mechanical and thermal properties
Minimum bending radius
occasional flexing: 10 x cable diameter
fixed installation: 4 x cable diameter
Temperature range
occasional flexing: - 15˚C up to +70˚C max. conductor temp.
fixed installation: - 40˚C up to +80˚C max. conductor temp.
Bending cycles and power chain
operation parameters
Power chain
limited to 2-7 cores and 0.5 2.5 mm²
Min. bending radius: 15 x outer diameter
temperature range: -5 °C up to +70 °C max. conductor temp.
Travelling distance up to 5 m: 0.2 … 1 million bending cycles
Torsional stress
in WTG:
TW-0 (5000 cycles at ≥ +5˚C)
TW-1 (2000 cycles at ≥ -20˚C)
± 150˚/m at 1 revolution per minute
Flammability
flame retardant acc. to IEC 60332-1-2 resp. VDE 0482-332-1-2
Oil resistance
acc. to DIN EN 50290-2-22 bzw. VDE 0819-102, TM54
Tests
acc. to IEC 60811, EN 50395, EN 50396
General requirements
These cables are conform to the EU-Directive 2014/35/EU (Low Voltage Directive)