Data Sheet

DATA SHEET
1121200
ÖLFLEX
®
CLASSIC 110 CY Black 0,6/1kV
valid from :
10.04.2008
elaborated by:
TE-K: M. Herb / R. Kraemer
Document: DB1121200EN page 1 of 1
All deviations from this specification are subject to explicit consent of U.I.LAPP GmbH. All rights reserved acc. to DIN 34.
No.: 0016/0894
Application
ÖLFLEX
CLASSIC 110 CY Black 0,6/1 kV cables are control- and connecting cables with a black outer sheath
for use in dry, damp and wet rooms, for normal mechanical load. Considering the indicated temperature range an
outdoor use is possible. At room temperature they are generally resistant against acids, caustic solutions and
certain oils. A continuous, busy movement, movements forced by the guide, usage of these cables in moving
cable carriers or on motor drum guidance or under a strain of more than 15 N / mm² is not allowed.
ÖLFLEX
CLASSIC 110 CY Black 0,6/1 kV is used as control- and connecting cable for control systems in
machine tools, transporting plants, production and assembly lines, as well as measuring systems, automatic
control and units of computer. ÖLFLEX
CLASSIC 110 CY Black 0,6/1 kV is mainly used on the export markets
where black outer sheaths are usual. The screen is a protection against electrical interference.
Design
Design in support to HD 21.13 S1 resp. VDE 0281-13 and
CEI-UNEL 35755 and 35756
Conductor fine wire strands of bare copper acc. IEC 60228 resp. VDE 0295, class 5
Core insulation LAPP special PVC compound P8/1, better than the PVC compound TI2
in acc. to HD21.1 resp. VDE 0281 part 1
Core identification acc. to VDE 0293-1, with or without gn/ye ground conductor
black cores with white numbers
acc. to DIN EN 50334 resp. VDE 0293 part 334
Inner sheath PVC compound TM2 acc. to HD21.1 resp. VDE 0281 part 1, colour black
Screen braid of tinned copper, coverage = 85% (nominal value)
Outer sheath PVC compound TM2 acc. to HD21.1 resp. VDE 0281 part 1, colour black
Electrical properties at 20 °C
Nominal voltage 600 / 1000 V
Test voltage 4000 V AC
Mechanical and thermal properties
Temperature range for flex. applications -5 °C up to +70 °C max. conductor temperature
fixed installation -40 °C up to +80 °C max. conductor temperature
Min. bending radius 6 x cable diameter for fixed installation
20 x cable diameter for flex. applications
Flammability flame retardant in acc. to IEC 60332-1-2 resp. VDE 0482-332-1-2
Tests acc. to IEC 60811-x-x resp. VDE 0473 part 811-x-x and VDE 0472
EC directive this cable confirms to ECD 2006/95/EC (low voltage directive)