Data Sheet
U.I. Lapp 
GmbH 
DAT
A SHEET
ÖLFLEX
®
 CLASSIC 130 H
DB 1123000 
valid from: 2013-07-31 
Originator: KASC / PDC
approved: HESC / PDC 
Document:  DB1123000EN  Page 1 of 2 
All rights reserved acc. to DIN ISO 16016. 
PD 0019/2.2_11.10EN 
Application 
ÖLFLEX
®
  CLASSIC  130  H  are  halogen  free,  highly  flame  retardant  control  cables,  designed  for  the  European  and  North 
American market, for occasional flexible use and fixed installation subject to normal mechanical load conditions. They are 
among others designed for use in dry, humid or wet conditions. Considering the temperature range, a temporary outdoor 
use  is  possible.  They  are  suitable  for  non-continuously  recurring  movement  without  tensile  load.  Continuous  operational 
movements, restricted guidance, usage of these cables in moving cable carriers or on motor drum guidance or under a strain 
of more than 15 N/mm² are not allowed. 
Application range: 
ÖLFLEX
®
 CLASSIC 130 H can be used in public facilities, airports, railway stations, plants engineering and constructions, air 
conditioning systems and particularly where human and animal life as well as valuable property are exposed to high risk of 
fire hazards. 
USE acc. to UL:   FRPE sheathed cable for internal wiring of appliances and external interconnection of electronic equipment 
Design 
Design  acc. to UL AWM 758, Style 21089 and 
  based on EN 50525-3-11 resp. VDE 0285-525-3-11 
Approvals    UL AWM 758, Style 21089 (File No. E63634) 
Conductor  fine wire strands of bare copper, acc. to IEC 60228 resp. VDE 0295, Class 5 
Core insulation  halogen free compound TI6 acc. to 
  EN 50363-7 resp. VDE 0207-363-7 
Core identification  acc. to VDE 0293-1, with or without GN/YE ground conductor 
  black cores with white numbers acc. to DIN EN 50334 resp. VDE 0293-334 
Outer sheath  halogen free compound TM7 acc. to EN 50363-8 resp. VDE 0207-363-8 
  color: silver grey, similar RAL 7001 
Electrical properties 
Nominal voltage  VDE U
0 
/ U:  300 / 500 V 
  UL:    600 V 
Test voltage  Core / Core:  4000 V AC 
Mechanical and thermal properties 
Min. bending radius  occasional flexing:   15 x outer diameter     
  fixed installation:    4 x outer diameter 
Temperature range  occasional flexing (VDE): -15 °C up to +70 °C max. conductor temp. 
  occasional flexing (UL):  -15 °C up to +75 °C max. conductor temp. 
  fixed installation (VDE):  -40 °C up to +80 °C max. conductor temp. 
  fixed installation (UL):  -40 °C up to +75 °C max. conductor temp. 
Flammability  flame retardant acc. to  IEC 60332-1-2 resp. VDE 0482-332-1-2 
        UL: Cable flame test 
  flame propagation acc. to IEC 60332-3-24 resp. VDE 0482-332-3-24 or 
        IEC 60332-3-25 resp. VDE 0482-332-3-25 