Data Sheet

U.I. Lapp
GmbH
DAT
A SHEET
ÖLFLEX
®
CLASSIC 110 SY
DB 1125752
valid from: 2013-03-08
Originator: KASC / PDC
approved: HAPF / PDC
Document: DB1125752EN Page 1 of 1
All rights reserved acc. to DIN ISO 16016.
PD 0019/2.2_11.10EN
Application
ÖLFLEX
CLASSIC 110 SY cables are VDE approved power and control cables for occasional flexible use and fixed installa-
tion under normal mechanical load conditions. They are for use in dry, damp and wet rooms. They may only be installed
outdoors with UV-protection and in observation of the temperature range. At room temperature it is widely resistant against
acids, caustics solutions and certain oils. ÖLFLEX
CLASSIC 110 SY suitable for freely moved without forced guidance and
tensile stress. The braid of galvanized steel-wires is an additional mechanical protection.
Application range:
ÖLFLEX
CLASSIC 110 SY cables are used in plant engineering, in industrial machinery and in heating and air conditioning
systems as well as in areas with high mechanical stress.
Design
Design based on
EN 50525-2-51resp. VDE 0285-525-2-51 / HD 21.13 S1 + A1 resp. VDE 0281-13
Approval VDE-Reg.-Nr. 7030
Conductor fine wire strands of bare copper, acc. to IEC 60228 resp. VDE 0295, class 5
Core insulation PVC compound TI2 acc. to EN 50363-3 resp. VDE 0207-363-3 with increased
requirements acc. to Lapp specification
Core identification acc. to VDE 0293-1, with or without GN/YE ground conductor
black cores with white numbers acc. to DIN EN 50334 resp. VDE 0293-334
Inner sheath PVC compound TM2 acc. to EN 50363-4-1 resp. VDE 0207-363-4-1
colour: silver grey, similar RAL 7001
Braid braid of galvanized steel-wires, coverage = 70 % (nominal value)
Outer sheath PVC compound TM2 acc. to EN 50363-4-1 resp. VDE 0207-363-4-1
colour: transparent
Electrical properties
Nominal voltage U
0
/ U: 300 / 500 V
Test voltage Core/Core: 4000 V AC
Core/Screen: 4000 V AC
Mechanical and thermal properties
Min. bending radius occasional flexing: 20 x outer diameter
fixed installation: 6 x outer diameter
Temperature range occasional flexing: -5 °C up to +70 °C max. conductor temp.
fixed installation: -40 °C up to +80 °C max. conductor temp.
Flammability acc. to IEC 60332-1-2 resp. VDE 0482-332-1-2
Tests acc. to IEC 60811, EN 50395, EN 50396
EC-Directives This cable is conform to the EC-Directives 2006/95/EC (Low Voltage Directive)
and 2011/65/EU (RoHS, Restriction of the use of certain hazardous substances).