ÖLFLEX 115 CY
DB1136752
valid from: 19.08.2014
Originator: ROKR / PDC
approved: HAPF / PDC
Document: DB1136752DE page 1 of 1
All rights reserved acc. to DIN ISO 16016.
PD 0019/2.2_11.10EN
Application
ÖLFLEX
1
15
CY
cables
are control cables for occasional flexible use and fixed installation
under
normal mechani
cal load
conditions. They are among others designed for use in dry, damp or
wet rooms. Outdoor use: They may only be installed with
UV protection and considering the temperature range. At room temperature they are widely resistant to acids, caustic solu-
tions and certain oils.
They are suitable for free, non-continuously recurring movement without tensile load. Continuous operational
movements,
restricted guidance,
usage of these cables in moving cable carriers or on motor drum guidance or under a strain of more than
15 N/mm² conductor cross-section are not allowed. The screen is a protection against electrical interference.
Application range:
Control units for machine tools, conveyor systems, measurement and control technology, systems for data processing.
Design
Design
Based on
EN 50525-2-51 ressp. VDE 0285-525-2-51
Conductor
F
ine
wire strand
s
of bare copper acc
. to
IEC 60228 resp.
VDE 0295, Class
5
Core i
nsulation
PVC compound
TI2 acc.
to DIN EN 50363
-
3 resp. VDE
0207
-
363
-
3
with increased requirements acc. to Lapp specification
Core identification code
a
ccording to VDE 0293
-
1, with
or without
GN/YE ground conductor
,
black cores with white numbers acc. to DIN EN 50334 resp. VDE 0293-334
Wrapping
P
lastic foil
Screen
Braid of tinned copper, coverage = 85% (nominal value)
Outer sheath
PVC compound
TM
2
acc. to
DIN EN 50363
-
4
-
1 resp. VDE 0207
-
363
-
4
-
1
Colour: Siver grey, similar RAL 7001
Electrical properties at 20°C
Nominal
voltage
300 / 500 V
Test voltage
C
ore/core
4000 V AC
Core/screen 2000 V AC
Transfer impedance
max. 250 m
Ω/m at 30 MHz
Mechanical and thermal properties
Minimum bending radius
Occasional fl
exing:
2
0
x
outer
diameter
Fixed installation: 6 x outer diameter
Temperature range
Occasional fl
exing
:
-
5
˚C up to +
7
0
˚C
max. conductor temp.
Fixed installation: - 40˚C up to +80˚C max. conductor temp.
Flammability
a
cc. to IEC 60332
-
1
-
2 resp. VDE
0482
-
332
-
1
-
2
Tests
a
cc. to IEC 60811, EN 50395, EN 50396
EC
-
D
irective
s
Th
i
s cable
is
conform to the EC
-
Directive
s
2006/95/EC (Low Voltage Directive)
and 2011/65/EG (RoHS, Restriction of the use of certain hazardous substances).