Data Sheet

DATA SHEET
0015003
ÖLFLEX
®
150 QUATTRO
valid from :
15.10.2009
Originator: R. Krämer / TE-K
approved: H. Schillinger / TE-K
Document: DB0015003EN page 1 of 2
All deviations from this specification are subject to explicit consent of U.I.LAPP GmbH. All rights reserved acc. to DIN 34.
No.: 0019/0408
Application
ÖLFLEX
®
150 QUATTRO cables are oil resistant power and control cables for occasional flexible use and fixed
installation for medium mechanical stresses. They are among others designed for use in dry, damp and wet
rooms. Due to their construction and the composition of material, they are approved in accordance with Euro-
pean, US - American and Canadian standards. They are not designed for outdoor use.
ÖLFLEX
®
150 QUATTRO cables are increased oil resistant and at room temperature they are widely resistant to
acids and alkali-resistant. They are suitable for free non-continuously recurring movement without tensile load or
compulsory guidance.
Application range:
Plant engineering and construction, industrial machinery, air conditioning installations, machine tools.
Design
Design construction standard H05VV5-F acc. to HD 21.13S1 resp. VDE 0281-13,
UL AWM Style 21098 or 2587,
CSA AWM C22.2 No. 210-05
Conductor fine wire strands of bare copper, acc. to IEC 60228 resp. VDE 0295, Class 5
Core Insulation PVC compound TI2 in acc. to HD 21.1 resp. VDE 0281 part 1,
UL-Class 43 / CSA 90 °C
Core identification acc. to VDE 0293-1, with or without GN/YE ground conductor
black cores with white numbers
acc. to DIN EN 50334 resp. VDE 0293-334
Outer sheath PVC compound TM5 in acc. to HD 21.1 resp. VDE 0281 part 1,
UL-Class 43 / CSA-90 °C
Electrical properties
Nominal voltage U
0
/U in acc. to HAR: 300 / 500 V
U in acc. to UL/CSA: 600 V
Test voltage 3000 V AC
Mechanical and thermal properties
Min. bending radius occasional flexing: 12,5 x cable diameter
fixed installation: 4 x cable diameter
Temperature range occasional flexing:
in acc. to HAR: -5 °C up to +70 °C max. conductor temp.
in acc. to UL/CSA: -5 °C up to +90 °C max. conductor temp.
fixed installation:
in acc. to HAR: -40 °C up to +70 °C max. conductor temp.
in acc. to UL/CSA: -40 °C up to +90 °C max. conductor temp.
Flammability HAR: In acc. with IEC 60332-1-2 resp. VDE 0482-332-1-2
UL: Vertical Flame Test in acc. to UL 1581 § 1061, UL VW-1,
CSA: FT1