Data Sheet

DATA SHEET
1550030
POWER CABLE NYY
valid from :
18.04.2006
elaborated by:
TE-K:
Document: DB1550030EN page 1 of 1
Nr.: 0019/0894
Application
NYY are cables with an insulation and an outer sheathing of PVC. They are used for fixed installation in dry or
damp rooms as well as outdoors, underground and under water. Multicore cables have a common core covering
over the twisted cores or a filler.
Design
Design in acc. to VDE 0276-603 that is 627 resp. HD 603 und 627
Conductor single wire conductors of in accordance to IEC 60 228 that is VDE 0295
Core insulation: PVC compound DIV4 in acc. to VDE 0276-603
Core colour code acc. with VDE 0293-308
Outer sheath PVC compound DMV5 in acc. to VDE 0276-603
Colour of outer sheath black
Electrical properties at 20° C
Working voltage 0,6 / 1 kV
Test voltage 4000 AC
Mechanical and thermal properties
Temperature range during installation: C up to + 50° C
after installation: -40 °C up to + 70° C.
Flame retardant in acc. to IEC 60 332.1
EC directive This cable confirms to ECD 73/23/EEC (low voltage directive).

Summary of content (1 pages)