Data Sheet

Product Information
Page 2 of 3
J-Y(ST)Y ..LG Indoor Cable Valid: 07.02.2012
Technical Data
Core identification code
according to VDE 0815, refer to Appendix T10
Approvals
VDE 0815
Peak operating voltage
(not for power applications) 300 V
Insulation resistance
> 100 MOhm x km
Coupling
(800 Hz): K1: 80% † 300 pF/100m
Conductor cross-section in
0.6 mm: 0.28 mm²
0.8 mm: 0.50 mm²
Cable attenuation/attenuation
0.6 mm: 1.7 dB/km
0.8 mm: 1.1 dB/km
Minimum bending radius
10 x outer diameter
Test voltage
Core/core: 800 V
Core/screen: 800 V
Loop resistance
0.6 mm: max. 130 ohm/km
0.8 mm: max. 73.2 ohm/km
Temperature range
Fixed installation: -30°C to +70°C
Article List
Part
number
Number
of double cores
Outer
diameter (mm)
Copper
index (kg/km)
Weight
(kg/km)
J-Y(ST)Y...LG copper conductor 0.6 mm
1591300 1 5.0 6.9 30
1591301 2 5.5 13.0 40
1591302 3 6.3 18.0 50
1591303 4 6.7 24.0 60
1591304 5 7.2 30.0 70
1591305 6 7.5 35.0 80
1591306 8 8.0 46.0 90
1591307 10 9.0 58.0 110
1591308 12 9.5 71.0 130
1591310 16 10.5 93.0 160
1591311 20 11.0 116.0 190
1591312 24 11.5 139.0 220
1591313 30 13.0 172.0 280
1591314 40 15.0 229.0 350
1591315 50 17.0 286.0 430
1591316 60 18.0 342.0 500
1591318 100 23.0 568.0 850
J-Y(ST)Y...LG copper conductor 0.8 mm