Application
H07RN-F are heavy duty rubber insulated /rubber sheathed cables designed for use subject to high mechanical load condi-
tions in dry or damp rooms, suitable for outdoor use. Continuous operational movements, restricted guidance, usage of
these cables in moving cable carriers or on motor drum guidance or under a strain of more than 15 N/mm² conductor cross
section are not allowed.
Single-core designs of heavy rubber cables H07RN-F can be used for short circuit- and earth-leakage-proof installation ac-
cording to VDE 0100-520 (VDE 0100-520).
Application range: In dry or damp rooms as well as outdoors taking into account all normative cable characteristics accord-
ing to VDE 0298-300 (VDE 0298-300); for use under medium mechanical loads, e.g. for equipment in industrial and agricul-
tural workshops, electric tools, transportable motors, machine tools.
Design
Design acc. to. EN 50525-2-21 (VDE 0285-525-2-21).
Conductor fine wire strands of bare copper, acc. to IEC 60228 resp. EN 60228 (VDE 0295), Class 5
Core insulation rubber compound EI4 acc. to EN 50363-1 (VDE 0207-363-1).
Core identification up to 5 cores
colour-coded acc. to VDE 0293-308 (VDE 0293-308)
with or without GN-YE ground conductor
starting at 6 cores
black cores with white numbers with GN-YE ground conductor
acc. to EN 50334 (VDE 0293-334).
Outer sheath rubber compound EM2 acc. to EN 50363-2-1 (VDE 0207-363-2-1).
Elektrical properties
Nominal voltage U
0
/U
450 / 750 V
Test voltage A / A 2500 V AC
Mechancal and thermal properties
Min. bending radius 4 to 8 x D acc. to VDE 0298-300 (VDE 0298-300); Tab. 6
Temperature range -25 °C bis +60 °C max. conductor temp.
Oil resistance acc. to EN 60811-404 (VDE 0473-811-404)
Flammability acc. to EN 60332-1-2 (VDE 0482-332-1-2)
Tests acc. to EN 60811-100 (VDE 0473-811-100),
EN 50395 (VDE 0481-395); EN 50396 (VDE 0473-396)
The cable is characterized with the HAR HAR-sign or HAR-identification thread.
EG-Directives These cables are conform to the EC-Directives 2006/95/EC (Low Voltage Directive),