Data Sheet

U.I. Lapp
GmbH
DATA SHEET
H05RN-F (X05RN-F)
DB1600250EN
valid from: 2011-05-31
Originator: T. Merker / PCM (PD-KL)
Document: DB1600250EN page 1 of 4
All rights reserved acc. to DIN ISO 16016.
PD 0019/2.2_11.10EN
APPLICATION
(HD 516/VDE 0298-300, HD 22.4/VDE 0282-4, HD 22.8/VDE 0282-8)
Low-voltage high-power current cable according to cable type standard HD (harmonisation document)
22.4 (= VDE 0282-4) or HD 22.8 (= VDE 0282-8)
Applications in households
Connection of hand-held inspection lamps
Connection of devices in kitchens and offices, examples:
o Vacuum cleaner
o Kitchenware
o Soldering gun
o Toaster
Light mechanical stress
Allowed kinds of water contact:
o Drops/Tears maximally
o No permanent contact
o No flooding
o No waves/swells
Suitability for permanent use outdoors with:
o Normal and light mechanical stress maximally
o Respect to:
o Absence of ozone resistance of the outer sheath compound EM 2 according to HD
22.1/VDE 0282-1
o Maximum conductor temperature of +60°C
o Maximum cable surface temperature of the outer sheath of +50°C
o Water contact at most with sporadic intensity in terms of drops/tears
Use as chain of lights, fairy lights or for similar decoration purposes:
o Temporally limited
o Indoors
o Outdoors
o For dimension ranges listed under HD 22.8/VDE 0282-8:
o All single-core dimensions
o Double-core dimensions with nominal conductor cross sections of 1.5 mm² or 2.5 mm²
General prevention of vibrations
Corrosive and polluting substances: Recurrent and accidental impact
Permitted permanent operation/system voltages:
(Rated IEC voltage class H05) (HD 22.1/VDE 0282-1, HD 22.4/VDE 0282-4, HD 22.8/VDE 0282-8):
o Phase/conductor-to-ground/PE (U
0
) 330 VAC, 495 VDC
o Phase/conductor (not PE)-to-phase/conductor (not PE) (U) 550 VAC, 825 VDC

Summary of content (4 pages)