Data Sheet

U.I. Lapp
GmbH
DATASHEET
J-Y(ST)Y...LG Fire Alarm Cable
1708002
14.11.2013
PN 0486/01_03.10
Technical Data
Number of pairs and conductor diameter (mm): 2 x 2 x 0,8
Outer diameter (mm): 7
Copper index (kg/km): 21
Weight (kg/km): 60
Core identification code: according to VDE 0815,
refer to Appendix T10
Peak operating voltage: (not for power applications)
300 V
Insulation resistance: > 100 MOhm x km
Coupling: (800 Hz): K1: 80% ≤ 300 pF/100m
Conductor cross-section in: 0.8 mm: 0.50 mm²
Cable attenuation/attenuation: 0.8 mm: 1.1 dB/km
Minimum bending radius: Fixed installation:
10 x outer diameter
Test voltage: Core/core: 800 V
Core/screen: 800 V
Loop resistance: max. 73.2 Ohm/km
Temperature range: Occasional flexing: -5°C to +50°C
Fixed installation: -30°C to +70°C
Powered by TCPDF (www.tcpdf.org)
Product Management Document: J-Y(ST)Y...LG Fire Alarm Cable
2 / 2
©2012 Lapp Group - Technical changes reserved
Photographs are not to scale and do not represent detailed images of the respective products.