Data Sheet

U.I. Lapp
GmbH
DATA SHEET
UNITRONIC BUS PB FD P 1 x 2 x 0,64
DB2170222
valid from: 28.10.2011
Originator: RAWE/PDC
approved: HAPF/PDC
Document: DB2170222 page 1 of 2
All rights reserved acc. to DIN ISO 16016.
PD 0019/2.2_11.10DE
Application
Highly flexible data cable for the SIEMENS field-net SINEC L2 DP (acc. to DIN 19245, part 3 and EN 50 170) for fieldbus
system FIP (Factory Instrumentation Protocol) as well as for high performance data networks with 150 Ω nominal
impedance. The cable is designed for the system-defined transmission rates of 1.5 MBit/s, 2.5 MBit/s and 12 MBit/s, the
transmission characteristics are conform to the system and guarantee a high operating security during the data
transmission. The used materials are halogen free.
The cable is intended for high flexible application in power chains, on permanently moving machines and linear robots. Due
to its double screening it is suitable for installation in electromagnetically demanding areas. The PUR-sheath is very resistant
against mineral oils and abrasion.
Design
Conductor bare copper, nom. 0.25 mm
2
(24 AWG)
Insulation
Skin-Foam-Skin PE, core nom. 2.55 mm
Core identification code cores red and green
Stranding 2 cores together with 2 fillers
Wrapping 1 layer non woven tape
Screening plastic-laminated aluminium foil, side with metal outwards, braid of tinned
copper wires, coverage nom. 85%
Outer sheath PU flame retardant and halogen free, violet similar to RAL 4001,
wall thickness nom. 1.0 mm, outer diameter: max. 8.0 mm
Electrical properties at 20° C
Resistance (loop) max. 145 Ω/km
Insulation resistance min. 5 GΩxkm
Mutual capacitance A/A: ca. 32 nF/km
A/S: ca. 49 nF/km
(at 800 Hz)
Inductance 800 Hz: ca. 0.82 mH/km
Characteristic impedance 9,6 kHz: 270 Ω ± 27
38,4 kHz: 185 Ω ± 18
3 bis 20 Mhz: 150 Ω ± 15
Line attenuation 9,6 kHz: max. 0.3 dB/100 m
38,4 kHz: max. 0.4 dB/100 m
4 MHz: max. 2.5 dB/100 m
16 MHz: max. 4.9 dB/100 m
Velocity of propagation nom. 0,81c
Transfer impedance up to 20 MHz max. 10 mΩ/m
Operating peak voltage 220 V (not for power purposes)
Test voltage U