Data Sheet

U.I. Lapp
GmbH
DATA SHEET
ÖLFLEX
®
CLASSIC 100 CY
DB 0035001
valid from: 2013-04-19
Originator: KASC / PDC
approved: HAPF / PDC
Document: DB0035001EN
All rights reserved acc. to DIN ISO 16016.
PD 0019/2.2_11.10EN
Application
ÖLFLEX
CLASSIC 100 CY cables are power- and control cables for flexible use and fixed installation for medium mechanical
use. They are for use in dry, damp and wet rooms. They may only be installed outdoors with UV-protection and in observa-
tion of the temperature range. At room temperature they are generally resistant against acids, caustics solutions and certain
oils. ÖLFLEX
CLASSIC 100 CY is suitable for freely moved without forced guidance and tensile stress. The screen is a pro-
tection against electrical interference.
Application range:
ÖLFLEX
CLASSIC 100 CY cables are used as supply and flexible connecting cable in industrial machinery, in plant engineer-
ing and in power stations, in heating and air conditioning systems.
Design
Design based on
EN 50525-2-51 resp. VDE 0285-525-2-51 / HD 21.13 S1 + A1 resp. VDE 0281-13
Conductor fine wire strands of bare copper, acc. to IEC 60228 resp. VDE 0295, Class 5
Core insulation PVC compound TI2 acc. to EN 50363-3 resp. VDE 0207-363-3 with increased
requirements to Lapp specification
Core identification acc. to. VDE 0293-1, with or without GN/YE protective conductor
with up to 5 cores: acc. to 0293-308 / HD 308 S2
more than 5 cores: acc. to ÖLFLEX color code
Inner sheath PVC compound TM2 acc. to EN 50363-4-1 resp. VDE 0207-4-1
colour: silver grey, similar RAL 7001
Braid braid of tinned copper, coverage = 85 % (nominal value)
Outer sheath PVC compound TM2 in acc. to EN 50363-4-1 resp. VDE 0207-363-4-1
colour: transparent
Electrical properties
Nominal voltage up to 1, 0 mm
2
: U
0
/ U 300 / 500 V
from 1, 5 mm
2
: U
0
/ U 450 / 750 V
fixed and protected installation: U
0
/ U 600 / 1000 V
Test voltage Core/Core: 4000 V AC
Core/Screen: 4000 V AC
Mechanical and thermal properties
Min. bending radius occasional flexing: 20 x outer diameter
fixed installation: 6 x outer diameter
Temperature range occasional flexing: -5 °C up to +70 °C max. conductor temp.
fixed installation: -40 °C up to +80 °C max. conductor temp.
Flammability acc. to IEC 60 332.1 resp. VDE 0482-332-1-2
Tests acc. to IEC 60811, EN 50395, EN 50396
EC-Directives This cable is conform to the EC-Directives 2006/95/EC (Low Voltage Directive) and
2011/65/EU (RoHS, Restriction of the use of certain hazardous substances).