Data Sheet

U.I. Lapp
GmbH
DATA SHEET
Multi-Standard SC 2.2
DB 4150100
valid from: 2013-07-11
Originator: KASC / PDC
approved: HAPF / PDC
Document: DB4150100EN page 1 of 1
All deviations from this specification are subject to explicit consent of U.I. Lapp GmbH. All rights reserved acc. to DIN 34.
PD 0019/2.1_11.09EN
Application
These multi standard wiring cables SC2.2 are UL, CSA and HAR (VDE)* approved and are designed for use for control cabi-
net wiring as well as for installation in protective tubes, applicable within the scope of the UL- or Canadian or European
standard specifications. They are especially qualified for wiring in industrial machines in accordance with NFPA 79. At room
temperature they are widely resistant to oils.
Application range: HAR: Wiring cable for internal wiring acc. to
DIN EN 50525-2-31 resp. VDE 0285-525-2-31
UL (MTW): acc. to ANSI/NFPA 70 (National Electrical Code)
UL (AWM): oil resistant wiring cable for internal wiring
CSA (TEW): oil resistant wiring cable for internal wiring of devices
Design
Design / Approvals H07V2-K HAR (*) acc. to DIN EN 50525-2-31 resp. VDE 0285-525-2-31
UL (MTW) acc. to UL 1063, File-No. E198296
UL (AWM) Style 10269 acc. to UL 758
CSA (TEW) acc. to C22.2 No. 127-09
*For the dimensions 0.5; 0.75; 1.0; 16; 50; 70; 95; 120 mm² as well for the colours GN, YE and multi-coloured cores (except
for GN YE) there are no HAR-approval available (X07V2-K)!
Conductor fine-wired core of tinned copper strands acc. to IEC 60228 resp. VDE 0295, Class 5
UL 758 and CSA C22.2
Core insulation special PVC based compound
Electrical properties
Nominal voltage HAR H07V2-K U
0
/U: 450 / 750 V AC
UL (MTW)/CSA (TEW) U: 600 V
UL (AWM): U: 1000 V
Test voltage 2500 V AC
Mechanical and thermal properties
Min. bending radius fixed installation: OD≤8 mm: 4 x OD** / 2 x OD***
8<OD≤12 mm: 5 x OD** / 3 x OD***
OD>12 mm: 6 x OD** / 4 x OD***
** at conventional usage; *** at cautious bending
Temperature range fixed installation: HAR, (UL) MTW: -40 °C up to +90 °C max. conductor temp.
UL (AWM), CSA (TEW): -40 °C up to +105 °C max. conductor temp.
Flame resistance HAR: IEC 60332-1-2 resp. VDE 0482-332-1-2
UL: VW-1
CSA: FT1
Oil resistance UL/CSA: 60°C oil rating
Tests acc. to IEC 60811 resp. VDE 0473 and VDE 0472, UL 1581 and CSA C22.2
EC directive This cable is conform to EC-Directives 2006/95/EC (Low Voltage Directive) and
2011 / 65 / EU (RoHS, Restriction of the use of certain hazardous substances).

Summary of content (1 pages)