Cut Sheet

ÖLFLEX
®
Harmonized European Hook-up Wire & Cordage
Construction
If not otherwise specied, all values relating to the product are nominal values. Photographs are not to scale and are not true representations of the products in question.
For current information go to our website.
Technical Data
Application Advantage
Approvals
Recommended Applications
Temperature Range:
- <HAR>/IEC: -40°C to +70°C
- UL/CSA: -40°C to +105°C
Nominal Voltage:
- H05V-K:
- <HAR>/IEC: 300/500V
- UL/CSA: 300V
- H07V-K:
- <HAR> /IEC: 450/750V
- UL/CSA: 600V
Test Voltage:
- H05V-K: 2000V
- H07V-K: 2500V
Conductor Stranding: Class 5 ne wire
Color Code: 00: Green/Yellow 07: Violet
01: Black 08: Pink
02: Blue 09: Orange
03: Brown 10: Yellow*
04: Red 11: Green*
05: White 14: Dark Blue
06: Gray
Approvals:
- H05V-K UL: AWM 1007 & 1569
Canada: CSA AWM I A/B
Additional: <HAR> H05V-K
CE & RoHS
- H07V-K: UL: MTW per UL 1063
AWM 1015
Canada: TEW
Additional: <HAR> H07V-K
CE & RoHS
Cable Attributes page 640
OIL
OR-02
FLAME
FR-02
MOTION
FL-02
MECH.
MP-01
Panel and machine wiring for domestic and export usage; internal wiring of
devices, electrical, and medical equipment
Only one inventory vs. two for domestic and export
consumption
13 standard color options
UL MTW (16 AWG & larger)
Available in large cardboard barrels for easy pull
(16 AWG & larger)
Embossed cable marking available upon request
This internationally approved hook-up wire was designed to meet North
American and European market requirements. It passes <HAR> H05V-K,
<HAR> H07V-K, UL AWM, UL MTW (16 AWG & larger), CSA TEW & CE.
Conductors: Finely stranded tinned copper
Insulation: PVC
H05V-K: UL AWM Style 1007 & 1569, UL/CSA; H07V-K: UL AWM Style 1015, UL MTW 1063, CSA
Multi-Standard <HAR> Hook-up Wire
Harmonized Hook-up Wire
Part
Number
Nominal Outer
Diameter
Copper
Weight
Approx.
Weight
(in) (mm) (lbs/mft) (lbs/mft)
H05V-K
22 AWG (0.50 mm
2
)
41804.. 0.098 2.5 3 6
20 AWG (0.75 mm
2
)
41805.. 0.102 2.6 5 8
18 AWG (1.00 mm
2
)
41806.. 0.110 2.8 6 10
H07V-K
16 AWG (1.50 mm
2
)
41604.. 0.134 3.4 10 15
14 AWG (2.50 mm
2
)
41605.. 0.157 4.0 16 25
12 AWG (4 mm
2
)
41606.. 0.181 4.6 26 30
10 AWG (6 mm
2
)
41607.. 0.201 5.1 39 48
Part
Number
Nominal Outer
Diameter
Copper
Weight
Approx.
Weight
(in) (mm) (lbs/mft) (lbs/mft)
8 AWG (10 mm
2
)
41608.. 0.268 6.8 65 81
6 AWG (16 mm
2
)
41609..* 0.354 9.0 103 126
4 AWG (25 mm
2
)
41610.. 0.402 10.2 161 195
2 AWG (35 mm
2
)
41611. . 0.461 11.7 226 268
1 AWG (50 mm
2
)
41612.. 0.547 13.9 323 376
2/0 AWG (70 mm
2
)
41613.. 0.630 16.0 452 521
3/0 AWG (95 mm
2
)
41614.. 0.717 18.2 613 693
4/0 AWG (120 mm
2
)
41615.. 0.780 19.8 774 864
* No <HAR> approval available for 6 AWG (X07V-K)
For Lapp part number, add the double digit color code (see above) to the part number prex in the table; e.g.: 16 AWG H07V-K green/yellow = 4160400
* No <HAR> for
yellow or green
wires ≥ 16 AWG
800.633.6339 • www.lapptannehill.com

Summary of content (1 pages)