Datasheet

U.I. Lapp
GmbH
DATA SHEET
H05V-K
DB8110001EN
valid from: 11
th
Sept. 2014
Originator: T. Merker / PCM
approved: ? / PDC
Document: DB8110001EN
All rights reserved acc. to DIN ISO 16016.
PD 0019/2.2_11.10EN
APPLICATION (HD 516)
H05V-K belongs to Europe’s harmonized, normative cable types and is designed according to the CENELEC harmonized third-party stand-
ard EN 50525-2-31 formerly: Meanwhile withdrawn harmonization document HD 21.3. H05V-K is a classic, single-layer insulated, single-
core, low-voltage hook-up wire, and that for stationary/ static and protected installation inside of devices/ appliances/ machines/ con-
trol cabinets (panels) etc. as well as inside or on lamps, since it only disposes of basic protection, but not additional error protection, in
line with modified IEC 60364-4-41/ HD 60364-4-41, for lack of an outer sheath/ jacket. Also, H05V-K is suitable for protected, station-
ary/ static installation inside of closed conduits and cable ducting systems. Unprotected laying on or under plaster as well as wiring
through unclosed or opening cable trunking systems shall only be permitted as part of security irrelevant signal and control circuits with
special extra-low voltage under 25 V AC to-ground or under 60 V DC to-ground. In wet or damp rooms and locations, unprotected laying is
completely forbidden. Under individual part numbers, different core insulation colours are offered for diverse application types. As packag-
ing type, 100-metre coils in small, flat cardboard boxes are applied.
ETIM 5.0 Class-ID: EC000993
ETIM 5.0 Class-Description: Single core cable
DESIGN (EN 50525-2-31)
Conductor Copper, bare, fine-wired/ finely stranded, conductor class 5 acc. IEC 60228
Nominal conductor cross section 0.5 mm² to and incl. 1 mm²
Core insulation PVC compound type TI 1 acc. EN 50363-3
Core insulation colours Diverse single colours
Diverse double colours (lengthways stripes)
CABLE TYPE CERTIFICATION (EN 50525-2-31)
VDE H05V-K
Exceptions without cable type certification:
Transparent core insulations
Core insulations with partly transparent multiple-colour combinations
ELECTRICAL PROPERTIES @ +20 °C
IEC rated voltage U
0
/U 300/500 V AC = 450/750 V DC
Conductor resistance IEC 60228, conductor class 5
Test voltage 2000 V AC
Compliance with low-voltage EC directive 2006/95/EC
MECHANICAL, THERMAL AND CHEMICAL PROPERTIES
Minimum bending radius (HD 516) Intended use: 4 x Outer diameter
Cautious bending: 2 x Outer diameter
Conductor temperature Stationary/ static operation (without vibration): -40 °C to +80 °C
Moved operation (not normatively intended): +5 °C to +70 °C
Laying/ handling: Min. +5 °C
Short-circuit and ground leakage: Max. +160 °C
Ambient temperature at storage: Max. +40 °C
Flame retardant IEC 60332-1-2
RoHS Chemical compliance with the EU RoHS II directive 2011/65/EU on the
Restriction of (the use of certain) Hazardous Substances

Summary of content (1 pages)