Datasheet

DATA SHEET
0026001
ÖLFLEX
®
HEAT 105 SC and 105 MC
valid from :
18.01.2008
elaborated by:
TE-K: M. Herb / R. Krämer
Document: DB0026001EN page 1 of 1
Nr.: 0019/0894
Application
ÖLFLEX
®
HEAT 105 SC and 105 MC single and multi cores, are insulated resp. surrounded with a heat resistant
PVC compound. They are suitable for use in dry and damp rooms, but not outside. In the case of room tempera-
ture they are generally resistant against acids, caustic solutions and certain oils. Continuous, busy movements,
usage of these cables in moving cable carriers, respectively on motor drum guidance or under a strain of more
than 15 N/mm² is not allowed.
Design
Conductor from 0,5 mm
2
:
fine strands of bare copper wires acc. to IEC 60228 resp. VDE 0295, class 5
Design single cores: SC
0,25 - 1,0 mm
2
in acc. to HD 21.7 resp. VDE 0281-7 (H05V2-K)
1,50 - 10,0 mm
2
in acc. to HD 21.7 resp. VDE 0281-7 (H07V2-K)
cables: MC in acc. to HD 21.12 resp. VDE 0281-12 (H05V2V2-F)
Core insulation PVC compound TI3 in acc. to HD 21.1 resp. VDE 0281-1
Identification acc. to VDE 0293-1, with or without gn/ye ground conductor
up to 5 cores coloured acc. to HD 308 S2 resp. VDE 0293-308
more than 5 cores acc. to ÖLFLEX colour code
Outer sheath PVC compound TM3 in acc. to HD 21.1 resp. VDE 0281-1
Electrical properties at 20 °C
Nominal voltage single cores: SC for 0,25 - 1,0 mm
2
: 300/500 V
for 1,50 - 10,0 mm
2
: 450/750 V
cables: MC 300/500 V
Test voltage 2500 V AC
Mechanical and thermal properties
Temperature range fixed installation -20 °C up to + 90 °C max. conductor temperature
for short time until + 105 °C max. conductor temperature
Min. bending radius SC: 4 x cable diameter for fixed installation
MC: 4 x cable diameter for fixed installation
15 x cable diameter for flex. applications
Flame retardant in acc. to IEC 60332-1-2 resp. VDE 482-332-1-2
Tests in acc. to IEC 60811-x-x resp. VDE 0473 part 811-x-x, VDE 0472
EC directive this cable confirms to ECD 2006/95/EC
(low voltage directive).