Application
UNITRONIC
Li2YCYv (TP)
is a data cable with low capacitance for wiring of data systems at transmission rates up to
10 Mbit/s and is qualified for the serial interfaces RS422 und RS485. The cable can be used as a signal-, control- and
measuring cable as well as for transmission of low, sensitive signals and high bit rates.
Decoupling by means of twisted pair cable design and the screen protects against electromagnetic interferences.
The cable with reinforced outer sheath is designed for fixed installation indoors and outdoors as well as for laying
directly in the ground. The cable can be used for solderless connections, e.g. connections with insulation displacement
technology and Maxi-Termi-Point wiring.
Design
7
-
wire strands of bare copper wires
Insulation
special
Polyolefin
-
based compound
Core identification code
according to DIN 47100
Stranding
cores twisted to pairs, pairs are stranded in layers, wrapping with foil on the outer layer
Screen
Braiding with tinned copper wires
Outer sheath
special PVC
-
based
compound
colour: black (RAL 9005)
Electrical properties at 20°
Loop resistance
max. 186.0
Ω/km (0.22 mm
²)
max. 115.0 Ω/km (0.34 mm²)
max. 78.4 Ω/km (0.5 mm²)
Specific insulation resistance
> 5 G
Ω x km
Mutual capacitance
C/C approx. 60 nF/km
C/S approx. 160 nF/km
(at 800 Hz)
Inductivity
approx. 0.65 mH/km
Characteristic impedance
100 ± 15
Ω (> 1 MHz)
V
elocity of propagation
nom. 0.66 c
Peak working voltage
250 V (not for power applications)
Test voltage
C/C: 2000 V
C/S: 1000 V
Mechanical and thermal properties
Bending radius
Flexing: 15 x cable Ø
Fixed installation: 6 x cable Ø
Temperature range
Flexing:
-
5
˚C up to +70˚C
Fixed installation: - 40˚C up to +80˚C
Flammability
flame retardant acc. to IEC 60332
-
1
-
2
EC directive
This cable is
conform to the EC
-
Directive 2002/95/EC and 2011/65/EC
(RoHS, Restriction of the use of certain hazardous substances).
Design based on standard VDE 0812