Datasheet

DATA SHEET
0035700
ÖLFLEX
®
140 CY
valid from :
23.04.2007
elaborated by:
TE-K: H. Schillinger / M. Herb
Document: DB0035700EN page 1 of 1
Nr.: 0019/0894
Application
ÖLFLEX
®
140 CY cables are oil-resistant control cables for flexible use and fixed installation for connecting from
production- and machine tools components together. They are for use in dry, damp and wet rooms. They may
only be installed outdoors with UV protection and in observation of the temperature range. ÖLFLEX
®
140 CY
cables are increased oil-resistant and at room temperature generally resistant against acids and caustics
solutions.
Continuous, busy movements, usage of these cables in moving cable carriers, respectively on motor drum
guidance or under a strain of more than 15 N/mm² is not allowed. The screen is a protection against electrical
interference.
Technical data
Design H05VVC4V5-K in accordance to HD 21.13 S1 that is VDE 0281-13
Conductor bare copper, fine wire strand in accordance to IEC 60228
that is VDE 0295, class 5
Core insulation PVC compound TI2 in accordance to HD 21.1 S4 that is VDE 0281-1
Identification black cores with white numbers with green/yellow ground conductor in accordance
to VDE 0293-1 and EN 50334 that is VDE 0293-334
Inner sheath PVC compound TM2 in accordance to HD 21.1 S4 that is VDE 0281-1
Screen braid of tinned copper, coverage =85 % (nominal value)
Outer sheath PVC compound TM5 in accordance to HD 21.1 S4 that is VDE 0281-1
Nominal voltage 300/500 V
Test voltage 3000 V AC
Temp. range for flexible use: -5 up to +70° C max. conductor temperature
fixed installation: -40 up to 70°C max. conductor temperature
Min. bending radius for flexible use: 20 x cable diameter
fixed installation: 6 x cable diameter
Flame retardant in accordance to IEC 60332-1-2 that is VDE 0482-332-1-2
Oil resistance in accordance to IEC 60811-2-1 that is VDE 0473-811-2-1
Approvals H05VVC4V5-K in acc. to HD 21.13 S1 that is VDE 0281-13
Tests in accordance to IEC 60811-x-x that is VDE 0473 part 811-x-x and VDE 0472
EC directive This cable confirms to ECD 2006/95/EEC (low voltage directive).