DATA SHEET
01575XX
DIN compensating cable KPL SY XX x 1,5
valid from :
01.12.2008
Originator: Frank Hörtnagl / PD-KL
Approved: Werner Körner / TE
Document: DB0157501EN page 1 of 1
All deviations from this specification are subject to explicit consent of U.I.LAPP GmbH. All rights reserved acc. to DIN 34.
No.: 0019/0408
Application
The compensating cables KPL Version SY XX x 1,5 mare multi-cored PVC insulated cables with steel wire
armouring which transmit the thermoelectric voltage of PtRh/Pt thermocouples. They are for flexible use and fixed
installation in dry and damp rooms with medium mechanical load. They may only be installed outdoors with UV
protection and in observation of the max. permitted temperature range. The steel wire armouring serves as
mechanical protection.
Design
Conductor 1,5 mm² (48 x 0,20 mm)
Conductor material RCB/SCB alloying, accuracy class 2 according DIN 43722
Positive conductor: Cu (copper)
Negative conductor: CuNi (cupronickel)
Core insulation PVC compound
Core identification Positive conductor: red
Negative conductor: white
Core layering Cores twisted together
Inner sheath PVC compound, colour: white
Armouring Galvanized steel wire braiding
Outer sheath PVC compound, colour: white
Electrical properties
Limiting deviation class 2 ± 60 µV (± 5,0 °C) / me asuring point temperature +1000 °C
Mechanical and thermal properties
Temperature range fixed installed: -40 °C upto + 80 °C
occasional flexing: -5 °C up to +70 °C
Minimum bending radius occasional flexing: 15 x cable diameter
Flammability flame retardant in acc. to IEC 60332-1-2 resp. VDE 0482-332-1-2

Summary of content (1 pages)