Datasheet

U.I. Lapp
GmbH
DATA SHEET
UNITRONIC
®
BUS ASI FD (TPE) A
DB 2170830
valid from: 02.02.2010
Originator: P. Samek / PDC
approved: H. Pfeffer / PDC
Document: DB2170830EN page 1 of 1
All deviations from this specification are subject to explicit consent of U.I. Lapp GmbH. All rights reserved acc. to DIN 34.
PD 0019/2.1_11.09EN
APPLICATION
UNITRONIC
BUS ASI FD (TPE) A is a field-bus cable with two cores for AS-INTERFACE (Actuator-Sensor Interface).
Networking system for the lower field area.
Data transmission for AS-Interface telegrams and power supply for AS-Interface slaves, master, repeater, extender and
sensors is done via this unscreened, geometrically-coded two-core flat cable. Contacting the conductors without stripping
the insulation by insulation-displacement-system of AS-I modules.
The oil-resistant outer sheath of this field-bus cable recommends its use in typical industrial environment, especially in wet
areas of automotive industry, machining centres, especially in combination with water-based and water-mixable cooling
lubricants.
The cable is intended for flexible application and permanent installation in interiors by low and high temperatures.
The cable can be used in power chains.
Approvals: UL AWM Style 2103
CSA AWM II A/B 105°C 300V FT1
DESIGN
Conductor tinned copper wires, 1.5 mm², finest wires in acc. to VDE 0295 class 6
Insulation TPE, oil resistant
Coding: brown and blue
Lay two cores flat parallel. The brown core is on the side of the „nose“
The cores must be powdered with talc and the cores must not stick together with the sheath
Sheath TPE, oil resistant, flame retardant
Sheath colour yellow, RAL 1012 Part no. 2170830 printing ink: black
Sheath colour black, RAL 9005 Part no. 2170831 printing ink: white
TECHNICAL DATA
Conductor resistance acc. to VDE 0295 ≤ 13.7 Ω/km
Specific insulation resistance ≥ 1 M Ω x km
Capacitance at 1 kHz ≤ 80 nF/km
Inductance 0.5 … 0.75 mH/km
Characteristic impedance 167 kHz 70 … 140 Ω
Operating Voltage ∼ 30 V
Operating Peak Voltage
(not for power purposes) 300 V
Test voltage 2 kV
Temperature range, static - 40 to + 105°C
Temperature range, for flexible use - 30 to + 105°C
Minimum bending radius, static 12 mm
Minimum bending radius, for flexible use 60 mm
Flame propagation flame retardant in acc. to IEC 60 332-1-2
/ UL 1581 Sec. 1100 (FT-2 flame test) and Sec. 1060 (FT-1)
Oil resistance and cutting oil resistance acc. to UL 758 Sec. 15 (60°C)
GENERAL REQUIREMENTS
RoHS: This cable is conform to RoHS directive (2002/95/EG)