Brochure
Table Of Contents
- Packard_2018_Catalog_00_Cover
- Packard_2018_Catalog_01_motor
- Packard_2018_Catalog_02_Blowers
- Packard_2018_Catalog_03_OEM
- Packard_2018_Catalog_04_CoolingSolutions
- Packard_2018_Catalog_05_components
- Packard_2018_Catalog_06_controls
- Packard_2018_Catalog_06_Controls
- Packard_2018_Catalog_06_Controls-320
- Packard_2018_Catalog_06_Controls-321
- Packard_2018_Catalog_06_Controls-322
- Packard_2018_Catalog_06_Controls-323
- Packard_2018_Catalog_06_Controls
- Packard_2018_Catalog_06_Controls-328
- Packard_2018_Catalog_06_Controls-329
- Packard_2018_Catalog_06_Controls
- Packard_2018_Catalog_07_electrical
- Packard_2018_Catalog_07_Electrical
- Packard_2018_Catalog_07_Electrical-346
- Packard_2018_Catalog_07_Electrical-347
- Packard_2018_Catalog_07_Electrical-348
- Packard_2018_Catalog_07_Electrical-349
- Packard_2018_Catalog_07_Electrical
- Packard_2018_Catalog_07_Electrical-356
- Packard_2018_Catalog_07_Electrical-357
- Packard_2018_Catalog_07_Electrical
- Packard_2018_Catalog_08_AirHandling
- Packard_2018_Catalog_09_Accessories
- Packard_2018_Catalog_10_Index
- Packard_2018_Catalog_11_BackCover
packardonline.com
|
800.334.1769
238
COOLING SOLUTIONS
|
TechTip
from Packard Academy
DION’s TIP
Dion Rohrer
Product Development Manager
In brazed plate heat exchangers (BPHE) the #1 mode of failure is freezing. Do
not cool water below 33˚ F. In water chiller applications the low pressure cut-out
on the refrigerant side should be set no lower than 28˚ F, based on evaporator
refrigerant pressure at this temperature.
Features
• Easy to install
• Compact size means it ts easily into conned spaces, especially when
replacing a much larger shell-and tube heat exchanger
• High Performance
• High turbulence created by corrugations in the plates results in closer
approach temperatures with much smaller units
• Fully brazed construction handles high operating pressures
• Copper brazed 316L stainless heat transfer plates
• Proven and Reliable
• UL listed and ASME Section VIII available
• Every heat exchanger is tested before it leaves the plant
Two Refrigerant Liquid Chillers
Maximum Allowable Working Pressure: 650 psig (45 Bar)
Item ID Nominal Tons
Standard Connections (IDS) (in.)
Depth (in.) Weight (lbs.)Ref. In Ref. Out Fluid
2 Circuit 10” x 20” Models (9.8”W x 20.3”H) - Low Pressure
CH10-2C 10 7/8 1 1/8 1 1/2" MPT 2.7 65
CH15-2C 15 7/8 1 1/8 1 1/2" MPT 3.8 77
CH30-2C 30 7/8 1 1/8 1 1/2" MPT 7.0 115
CH35-2C 34 7/8 1 1/8 1 1/2" MPT 8.5 131
CH50-2C 50 1 1/8 1 1/2 2 1/2 MPT 12.1 173
CH60-2C 60 1 1/8 2 1/8 2 1/2 MPT 13.9 194
2 Circuit 10” x 20” Models (9.8”W x 20.3”H) - High Pressure XP
CH10-2C-XP 10 7/8 1-1/8 1-1/2" MPT 2.8 91
CH15-2C-XP 15 7/8 1-1/8 1-1/2" MPT 3.9 104
CH20-2C-XP 20 7/8 1-3/8 1-1/2" MPT 5 116
CH25-2C-XP 25 7/8 1-3/8 2" MPT 6.1 128
CH30-2C-XP 30 7/8 1-3/8 2" MPT 7.1 140
CH35-2C-XP 35 7/8 1-3/8 2" MPT 8.4 155
CH40-2C-XP 40 7/8 1-5/8 2-1/2" MPT 9.7 169
CH50-2C-XP 50 1-1/8 1-5/8 2-1/2" MPT 12.2 197
CH60-2C-XP 60 1-1/8 2-1/8 2-1/2" MPT 14 218
KELVION BRAZED PLATE HEAT EXCHANGERS
Maximum Allowable Working Pressure: 450 psig (31 Bar)