Brochure

packardonline.com
|
800.334.1769
326
CONTROLS
|
Potential Relays
Item ID Mfg. # Industry #
Continous Coil
voltage Pick up MIN Pick Up Max Drop-Out Max
Packard
TR63 3ARR363223PR 19002 170V 136V 156V 58V
TR64 3ARR364252PR 19003 395V 257V 278V 123V
TR65 3ARR36533PR 19004 332V 165V 185V 93V
TR66 3ARR366252PR 19005 395V 210V 230V 123V
TR67 3ARR367262PR 19006 420V 292V 318V 130V
TR68 3ARR36843PR 19007 500V 322V 348V 138V
TR69 3ARR369243PR 19008 336V 177V 198V 108V
TR70 3ARR37053PR 19009 253V 282V 308V 80V
TR71 3ARR37163PR 19010 420V 209V 235V 124V
Item ID Mfg. # Industry #
Continous Coil
voltage Pick up MIN Pick Up Max Drop-Out Max
Packard
TR550 3ARR355071PR 19550 130V 111V 134V 42V
TR551 3ARR355132PR 19551 332V 243V 271V 91V
Item ID Description
Packard
TRQC6 Package of six (6) double quick connect terminals with screws
Features
Universal replacements for thousands of GE 3ARR3 model relays and many
other OEM’s
Manufactured using the original GE designs and tooling
Proven performance for 40 years
Contact rating: 35 amps max, break only
Endurance up to 500,000 operations depending on load
Screw type terminals #8-32 thread
Six (6) quick connect terminals and screws packaged included with each relay
Instructions included
UL approved
Applications:
Central air conditioner compressors
Submersible pump motors
Motors generally over 1/3 HP with start capacitors
Internal Wiring Diagrams
TR550
TR551
TR63
TR64
TR65
TR66
TR67
TR68
TR69
TR70
TR71
RELAYS