PW-311: 120/240/277VAC; 50/60Hz
PW-311-347: 347VAC; 50/60Hz
Dimming control signal: 0-10VDC, sinks up to 50mA for
control of compatible ballasts (25 if each sources 2mA);
Class 1 wiring
Time delays: 3, 5, 15 or 30 minutes, walk-through, test-mode
Power up after power loss: On, Off or last state
Coverage: Major motion 35’ x 30’, Minor motion 20’ x 15’
Sensitivity adjustment: PIR (high/low)
Dimensions (L x W x D): 2.73” x 1.75” x 1.81” (69mm x 44mm
x 46mm)
UL and cUL listed (E101196). Complementary Listed to
“Emergency Lighting Equipment, (UL924)
Five year warranty
SPECIFICATIONS
For best performance, Legrand recommends using
this sensor in spaces no larger than 15’ x 12’.
PIR
Coverage
7.5’
(2.2m)
15’
(4.5m)
20’
(6.1m)
35’
(10.6m)
Major motion
Minor motion
4’
(1.2m)
20’
(6.1m)
35’
(10.6m
)
0
DELAY
MODE
ADDITIONAL
FEATURES
Button
Hinges
Tabs
Dip Switches
Detection LE
D
PIR Lens
Up Button
Down Button
COVERAGE PATTERNS
CONTROLS & SETTINGS
Product Controls DIP Switch Settings
=ON =OFF
1
Auto - On
Manual - On
Mode
9
12345678
Time
Delay
Mode
ON
Additional
Features
Unused
Test/3 min
15 minutes
30 minutes
5 minutes
23
Time Delay
Exit Programming Mode
Audio Alert
Walk-Thru
Visual Alert
67
Additional Features
89
PIR Sensitivity
High Trim
Low Trim
Ramp Up Time
Fade Down Time
Light Level Adjust
Power Loss Mode
Presentation Mode
Service Mode
Preset On Level
Non-Dim Mode
Green LED # of Blinks
1=OFF, 2=ON
1=ON, 2=OFF
1=OFF, 2=ON
1=100%, 2=50%
1=1, 2=2.5, 3=5, 4=10 seconds
1=2.5, 2=5, 3=15, 4=30 seconds
1=Last Non-Zero Value,
2=50%, 3=75%, 4=100%
1=10V, 2=Manual Adjustment
1=0V, 2=Manual Adjustment
1=Disable, 2=Enable,
3=Smart Light Level
Reset To Default
1=Keep Last State,
2=Default On, 3=Default Off
1=OFF, 2=ON
1=ON, 2=OFF
Press and Hold UP or
DOWN for 5 seconds
1=OFF, 2=ON
Default Values Shown