INPUT
Rated voltage and tolerance 230 Vac +15% -20%
Rated current 19.3 Arms
Power Factor PF > 0.99
Input current THD THDi < 3%
OUTPUT
Maintenance voltage 13.75 Vdc/battery
Rated current (max) 15 Adc
AC/DC Efficiency >93% at max rated current
INDICATIONS
Operating mode
(multi-color LED on the module
and display menu information
on the UPS)
Yellow LED, Fast intermittent: f1 recharge fase.
Green LED, Slow intermittent: f2 recharge fase and maintenance.
Green LED, fi xed: stand-by
Red LED: Fault mode
STANDARD
EN 62040-1, EN 62040-2, EN 62040-3
Bcm technical specifications
2. Technological description
3 104 36
10 kVA
3 104 37
15 kVA
3 104 37
20 kVA
3 104 39
30 kVA TM
3 104 38
30 kVA TT
3 104 40
40 kVA
3 104 41
60 kVA
Operating temperature 0°C ÷ 40°C
Relative humidity 20% ÷ 80% non-condensing
Noise level at 1m 58 ÷ 62 dBA
Grade of protection IP 21
Maximum altitude up to 1000m without derating