Trimod® INVERTER
- No. 1 UPS Trimod® unit;
- No. 1 bag of accessories with a set of screws for installing the unit correctly;
- No. 1 front closing panel;
- No. 2 base strips for side closing;
- Operating and maintenance manual
- International guarantee.
Trimod® BATTERY
- No. 1 Trimod® BATTERY cabinet;
- Operating and maintenance manual
- No. 1 multicore cable for connecting to the UPS Trimod® inverter;
- No. 1 bag containing fuses and keys for the front door.
Trimod®/2 BATTERY
- No. 1 Trimod® BATTERY/2 cabinet;
- Operating and maintenance manual
- No. 2 multicore cables for connecting to the UPS Trimod® inverter;
- No. 1 bag containing fuses and keys for the front door.
Check that the UPS Trimod® technical data on the plate on the sticker affixed on the inside panel of the door, inside the
hatch of the UPS, correspond to the material bought, described on the delivery document.
4.4 Storing
4.4.1 UPS
If the UPS is going to be stored prior to installation, regardless of whether or not it is still packed, it must be on dry, clean
and fresh premises where the ambient temperature is between 0°C and +50°C (32-122°F) and with humidity below 90%
(not condensing).
4.4.2 Batteries
The standard batteries of the UPS Trimod® are sealed lead-acid, they are maintenance-free and installed internally.
Lead is a dangerous substance for the environment if it is not recycled by specialized companies. If the batteries are not
charged they cannot be kept for more than 6 months at 20°C (68°F) or more than 3 months at 30°C (86°F) or more than 2
months at 35°C (95°F).
ATTENTION:
sealed batteries must never be stored if they are partly or totally flat.
To charge the batteries before and after storing, simply connect the input power supply to the UPS, plug in battery fuses
(F B+ and F B-) and then close the switches. When the unit detects the input voltage it automatically proposes starting a
battery charging cycle. After about 1 minute charging starts automatically and the time left to finish charging is shown
on the display. The charging cycle can be stopped at any time by pressing the ‘ESC’ key.
If the UPS is delivered without batteries, LEGRAND® is not liable for any damage or bad operation caused to it by an
incorrect wiring of the batteries.