5.3.2 THREE-PHASE input, SINGLE-PHASE output connection
For this type of connection, besides the wiring shown in the following figure, the software has to be configured via the
instrument panel as illustrated in paragraph 6.4 STARTING PROCEDURE.
ATTENTION
If the UPS is used with a single-phase output (available on 10/15/20/30TM models) you will have to plug in all the
‘Back Panel’ cards in the connector supplied in the accessory kit.
The ‘Back Panel’ cards are located inside the machine behind the power modules.
There is only one ‘Back Panel’ card in the Trimod® 10/15/20 models while in the Trimod® 30TM there are two. To
access the ‘Back Panel’ cards and insert the connector, simply extract 3 power modules that are on the same shelf
and refer to the following figure. The connector must be inserted in the position indicated with EC 15 on the card
serigraphy. To extract the power modules please consult the MAINTENANCE chapter.
UPS Trimod
®
10/15/20/30TM