PM status
Battery X
Voltage Voltage measured at the ends of the batteries by the power module X [V]
Current
Current required to the batteries from the power module X (negative if the
batteries are being charged) [A]
Batt. Charger Status of the battery charger inside module X
Misc. X
INV. dissip. Temp. Temperature of the INV dissipater (Inverter) of the power module X [°C]
BST dissip. Temp. Temperature of the Booster /PFC dissipater of the power module X [°C]
Fan speed Fan speed expressed as a percentage of the power module X
HV Bus pos. Voltage on the DC BUS positive of the power module X [V]
HV Bus neg. Voltage on the DC BUS negative of the power module Xm [V]
PM
Historical
Data X
Run Time Total time working
Batt.Time Total time running on battery
CarBatt.Time Total time the battery charger has been working
Bypass int. Total number of Bypass interventions
Battery int. Total number of battery interventions
Dumper int. Total number of Dumper interventions
T mains high
Total number of times the input mains voltage has exceeded the maximum
value allowed by the power module
No.Overheat. Total number of overheatings
No. Overloads Total number of overloads
No. HV Bus run Total number of overvoltages on the Bus
No. Out DC Level Total number of continuous voltage presences in output from the PMs
7. Control Panel
INDICATION
Press ENTER to change the X value and consequently vary the power module from where you read data.
Diagnostics (*)
Reset PM
Errors
Deletes the memory of errors found in the power
module. Resets only resettable errors.
PM SW update (*)
Update all
the PMs
It allows the sequential and automatic updating of the internal
software of all the UPS power modules. Press “ENTER” to start the
procedure. If the update is unnecessary the following message
appears on the display:
“PM SW versions updated!” Press “ESC to exit the frame.
Update a
single
PM
It allows the updating of the internal software of a single power
module. Using the ARROW” keys you select the module you wish to
update (‘PM00’ indicates the module at the top on the left, going
on to the last one at the bottom on the right).
By pressing “ENTER” key a frame appears that gives a comparison
between the software that is actually in the module selected and
the software you are about to load. Press “ENTER” to start the update
procedure.
Once updated, the message “PM SW version updated!” appears on
the display. Press “ESC” to exit the frame.
(following)
(*) Available in the “Service Mode” only