User's Manual

11
terminal box wiring holes, ensure the safety and insulation effect.
6 When using a small sectional cable, such as 4mm squared, the cable must be placed in the
medium to ensure that the screw is well tightened without deviation.
7 The cables should be connected correctly according to the wiring diagram and the terminals
should be tightened during the installation in order to avoid any damage caused by bad
connection.
The bad fixing of connection screws will lead to the raise of resistance,
which can lead to electrical energy loss and heating of terminals. The
heating of component is risky. Besides, 1mΩ contact resistance in a circuit
of 80A will result in 6.4 W power losses.
8 The cables should be connected correctly according to the definition of the auxiliary
terminal (such as pulse output, signal input or RS485 communication).
Be attention to not be mistakenly connected the auxiliary terminal to the
voltage or current line, so as to avoid damage to meter.
9 Check connecting wire carefully and avoid any error (such as the reverse wiring for the
incoming and outgoing lines, the wrong connection of live and neutral, the bad fixing of screws).
To ensure the correct wiring, it is recommended to use the appropriate
testing tools (such as multi-meters) for input/output test.