User Manual

AHR SERIESAHR SERIES
AC/DC Current TransducersAC/DC Current Transducers
Ranges 500 to 2000ARanges 500 to 2000A
4-20mA, 0-5 or 0-10 VDC Outputs4-20mA, 0-5 or 0-10 VDC Outputs
True RMSTrue RMS
Installation guideInstallation guide
Manuel d’installationManuel d’installation
Installation handleitungInstallation handleitung
Output SignalOutput Signal 0-5VDC or 0-10VDC0-5VDC or 0-10VDC
or 4-20mAor 4-20mA
Output LimitOutput Limit
B5/10 B5/10 7VDC for 5V output7VDC for 5V output
and and 14VDC for 10V output14VDC for 10V output
B420 B420 25mA25mA
Frequency RangeFrequency Range (+/- 1%) DC &(+/- 1%) DC &
20-6000 Hz 20-6000 Hz (All(All
Waveforms)Waveforms)
Response TimeResponse Time To 90% of step change.To 90% of step change.
150ms150ms
AccuracyAccuracy 1% FS1% FS
Power SupplyPower Supply 20-50VDC Nominal20-50VDC Nominal
Output Load for voltage outputOutput Load for voltage output
10 k10 k min recommended. min recommended.
Output Load for current outputOutput Load for current output
300 300 max recommended. max recommended.
Isolation VoltageIsolation Voltage 5 kV5 kV
EnvironmentalEnvironmental -40 to 70 Deg. C-40 to 70 Deg. C
-40 to158 Deg. F-40 to158 Deg. F
0-95% RH, non-0-95% RH, non-
condensingcondensing
SpecificationsSpecifications
LEM is a Swiss company serving marketsLEM is a Swiss company serving markets
connected with the transformation and useconnected with the transformation and use
of electricity. It designs, develops andof electricity. It designs, develops and
manufactures high-performance solutions,manufactures high-performance solutions,
ranging from active components to theranging from active components to the
most complex measuring systems.most complex measuring systems.
Diagram 1Diagram 1
Made to MeasureMade to Measure
This product is not intended for life or safety applications. This product is not intended forThis product is not intended for life or safety applications. This product is not intended for
installation in hazardous or classified locations.installation in hazardous or classified locations.
Potential electrocution hazard exists. Installing sensors in an energized motor control cenPotential electrocution hazard exists. Installing sensors in an energized motor control cen
ter or on any energized conductor can be hazardous.ter or on any energized conductor can be hazardous.
Read instructions thoroughly prior to installation.Read instructions thoroughly prior to installation.
This transducer shall be used in accordance with manufacturer instruction.This transducer shall be used in accordance with manufacturer instruction.
Power supply shall be a low voltage source and shall have an efficient protective systemPower supply shall be a low voltage source and shall have an efficient protective system
against over current.against over current.
The temperature of the primary conductor shall not exceed 100°CThe temperature of the primary conductor shall not exceed 100°C
This transducer shall be used in an electric/electronic equipment in respect of standardsThis transducer shall be used in an electric/electronic equipment in respect of standards
rules and applicable safety requirements.rules and applicable safety requirements.
When operating the transducer, certain parts of the module can carry dangerous hazardousWhen operating the transducer, certain parts of the module can carry dangerous hazardous
voltage. Ignoring the warning can lead to serious injury and/or cause damage.voltage. Ignoring the warning can lead to serious injury and/or cause damage.
This transducer is a built in device, of which conducting parts must be inaccessible byThis transducer is a built in device, of which conducting parts must be inaccessible by
installation.installation.
The operator must have accrediation to install this material.The operator must have accrediation to install this material.
1.1. Mount the transducer to a surface ifMount the transducer to a surface if
needed.needed.
2.2. Connect output wiring.Connect output wiring.
- - 0-5/10 VDC Model0-5/10 VDC Model: Make sure output: Make sure output
load is at least 10 kload is at least 10 k..
- - 4-20mA Models4-20mA Models: Make sure: Make sure
connection is correct (see diagram 1).connection is correct (see diagram 1).
3.3. Insert the wire in the transducer’s hole.Insert the wire in the transducer’s hole.
InstallationInstallationIMPORTANTIMPORTANT
DiagramsDiagrams
AHR-B420AHR-B420
AHR-B5/10AHR-B5/10
8, chemin des Aulx8, chemin des Aulx
1228 Plan-les-Ouates1228 Plan-les-Ouates
Geneva, SwitzerlandGeneva, Switzerland
www.lem.comwww.lem.com
(+)
(-)
24 VDC Power
(Controller, meter etc)
Load
(-)
(+)
10k
Output Connector
1(+) 2(out) 3(none) 4(GND)
AHR
Output Connector
1(+) 2(out) 3(none) 4(GND)
(+)
(-)
24 VDC Power
(Controller, meter etc)
Load
(-) (+)