Datasheet

Electrical data
Primary Nominal Current Output Voltage (Analog) Type RoHS since
I
PN
(A.t.rms) V
OUT
(V DC) date code
10,25,50 0-5 or 0-10 AP 50 B10 46320
50,75,100 0-5 or 0-10 AP 100 B10 46333
100,150,200 0-5 or 0-10 AP 200 B10 47282
200,300,400 0-5 or 0-10 AP 400 B10 planned
R
L
Load resistance 10 k
V
C
Supply voltage + 24 ± 5%V DC
I
C
Current Consumption < 30 mA
V
SL
Output voltage limitation (0-10V) 14 V
V
SL
Output voltage limitation (0-5V) 7 V
Î
P
Overload capability no limitation
Accuracy-Dynamic performance data
X Accuracy @ I
PN
, T
A
= 25°C (excluding offset) < ± 1 % of I
PN
ε
L
Linearity error (0 .. ± I
PN
) < ± 0.5 % of I
PN
V
OE
Electrical offset voltage @ T
A
= 25°C < ± 0.5 % of I
PN
TCV
OE
Temperature coefficient of V
OE
± 1 mV/K
TCV
OUT
Temperature coefficient of V
OUT
(% of reading) ± 0.1 %/K
t
r
Response time to 90% of I
PN
step < 150 m s
BW Frequency bandwidth (± 1 %) 30 .. 2000 Hz
General data
T
A
Ambient operating temperature - 20 .. + 60 °C
T
S
Ambient storage temperature - 20 .. + 85 °C
m Mass 90 g
IPxx Protection degree IP20
AC Current transducer AP-B10
Split-core transducer for the electronic measurement AC sinusoidal
waveform currents, with galvanic isolation between the primary circuit
(high power) and the secondary circuit (electronics). Switch selectable
measuring ranges and RMS 0-5V and 0-10V switch selectable voltage
output.
I
PN
= 10 .. 400 A
Features
RMS output (average)
Split-core type
0-5 VDC and 0-10 VDC switch
selectable voltage output
DIN rail or Panel mounting
Switch selectable measuring ranges
Isolated plastic case recognized
according to UL94-V0.
Advantages
Large aperture for cable up to
Ø18mm
High isolation between primary and
secondary circuits
Eliminates insertion loss
Easy installation
Applications
Automation systems
Analog current reading for remote
monitoring (e.g. motor) and
software alarms.
Panel meters
Simple connection to power
consumption displays.
Application domain
Energy and Automation
080212/5 www.lem.com
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/4

Summary of content (4 pages)