I
PN
= 5 .. 150 A
Features
RMS (average) output
0-10V DC voltage output
Split-core type
Ø 16 mm sensing aperture for
non-contact measurement
Terminal output
Isolated plastic case recognized
according to UL 94-V0.
Advantages
High isolation between primary
and secondary circuits
Compact case
Cost-effective solution
Easy installation
Applications
Automation and Supervision
Current measurement for process
regulation by distributed PLCs
or remote control (e.g. SCADA
software)
Safety and Condition
Monitoring
Load monitoring for protection
systems and predictive
maintenance (e.g. conveyers,
pumps or HVAC motors)
Application domain
Energy and Automation
Electrical data
Primary nominal current rms Output voltage Type
I
PN
(A.t.Rms) V
OUT
(V DC)
5 0-10 AT 5 B10
10 0-10 AT 10 B10
20 0-10 AT 20 B10
50 0-10 AT 50 B10
100 0-10 AT 100 B10
150 0-10 AT 150 B10
R
L
Load resistance 2 MW
V
C
Supply voltage self-powered
V
SZ
Output clamping voltage 15 V
Î
P
Overload capability - continuous 120 % of I
PN
- 1 min 150 % of I
PN
Performance data
X Accuracy @ I
PN
, T
A
= 25°C (excluding offset) < ± 2 % of I
PN
ε
L
Linearity error < ± 0.5 %
t
r
Response time to 90% of I
P
step < 300 m s
BW Frequency bandwidth 50/60 Hz
General data
T
A
Ambient operating temperature - 20 .. + 60 °C
T
S
Ambient storage temperature - 20 .. + 85 °C
m Mass 90 g
IPxx Protection degree IP40
I
PN
= 5 .. 150 A
AC Current transducer AT-B10
Split-core transducer for the electronic measurement of AC waveform
currents, with galvanic isolation between the primary circuit (power) and the
secondary circuit (measurement). 0-10V DC voltage output proportional to
the RMS value of the primary current.
071115/4 www.lem.com
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3
Features
RMS (average) output
0-10V DC voltage output
Split-core type
Ø 16 mm sensing aperture for non-
contact measurement
Terminal output
Isolated plastic case recognized
according to UL 94-V0.
Advantages
High isolation between primary and
secondary circuits
Compact case
Cost-effective solution
Easy installation
Applications
Automation and Supervision
Current measurement for process
regulation by distributed PLCs or
remote control (e.g. SCADA
software)
Safety and Condition Monitoring
Load monitoring for protection
systems and predictive
maintenance (e.g. conveyers,
pumps or HVAC motors)
Application domain
Energy and Automation
AC Current transducer AT-B10
Split-core transducer for the electronic measurement of AC waveform
currents, with galvanic isolation between the primary circuit (power)
and the secondary circuit (measurement). 0-10V DC voltage output
proportional to the RMS value of the primary current.
Electrical data
Primary nominal Output voltage Type
current rms
I
PN
(A.t.Rms) V
OUT
(V DC)
5 0-10 AT 5 B10
10 0-10 AT 10 B10
20 0-10 AT 20 B10
50 0-10 AT 50 B10
100 0-10 AT 100 B10
150 0-10 AT 150 B10
R
L
Load resistance ≥ 2 MW
V
C
Supply voltage self-powered
V
SZ
Output clamping voltage 15 V
Î
P
Overload capability - continuous 120 % of I
PN
- 1 min 150 % of I
PN
Performance data
X Accuracy @ I
PN
, T
A
= 25°C (excluding offset) < ± 1.5 % of I
PN
e
L
Linearity error < ± 0.5 %
t
r
Response time to 90% of I
PN
step < 300 ms
BW Frequency bandwidth 50/60 Hz
General data
T
A
Ambient operating temperature - 20 .. + 60 °C
T
S
Ambient storage temperature - 20 .. + 85 °C
m Mass 90 g
IPxx Protection degree IP40