Datasheet

Electrical data
Primary nominal Primary current Type RoHS since
current rms measuring range
4)
date code
I
PN
(A) I
PM
(A)
200 ± 600 HAT 200-S planned
400 ± 1200 HAT 400-S 46115
500 ± 1500 HAT 500-S 46129
600 ± 1800 HAT 600-S 46115
750 ± 2250 HAT 750-S planned
800 ± 2400 HAT 800-S 46115
1000 ± 3000 HAT 1000-S 46097
1200 ± 3000 HAT 1200-S planned
1500 ± 3000 HAT 1500-S 46158
V
C
Supply voltage (± 5 %)
4)
± 15 V
I
C
Current consumption ± 15 mA
R
IS
Isolation resistance @ 500 VDC > 1000 M
V
OUT
Output voltage (Analog) @ ± I
PN
, R
L
= 10 k, T
A
= 25°C ± 4 V
R
OUT
Output internal resistance 100
R
L
Load resistance > 10 k
Accuracy-Dynamic performance data
X Accuracy @ I
PN
, T
A
= 25°C (excluding offset) < ± 1 % of I
PN
ε
L
Linearity error
1)
(0 .. ± I
PN
) < ± 1 % of I
PN
V
OE
Electrical offset voltage @ T
A
= 25°C < ± 20 mV
V
OH
Hysteresis offset voltage @ I
P
= 0;
after an excursion of 1 x I
PN
< ± 10 mV
TCV
OE
Temperature coefficient of V
OE
< ±
1 mV/K
TCV
OUT
Temperature coefficient of V
OUT
(% of reading) < ±
0.1 %/K
t
r
Response time to 90% of I
PN
step < 5 µs
BW Frequency bandwidth
2)
(- 3 dB) DC .. 25 kHz
General data
T
A
Ambient operating temperature - 10 .. + 80 °C
T
S
Ambient storage temperature HAT 200-S, HAT 500..1500-S - 15 .. + 85 °C
HAT 400-S - 25 .. + 85 °C
m Mass 300 g
Current Transducer HAT 200..1500-S
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
I
PN
= 200..1500 A
V
OUT
= ± 4 V
Notes :
1)
Linearity data exclude the electrical offset.
2)
Please refer to derating curves in the technical file to avoid excessive
core heating at high frequency.
3)
Please consult characterisation report for more technical details and
application advice.
4)
Operating at ±12V Vc < ±15V will reduce the measuring range.
061128/10 www.lem.com
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3
Features
Hall effect measuring principle
Galvanic isolation between primary
and secondary circuit
Isolation voltage 3000 V
Low power consumption
Extended measuring range(3 x I
PN
)
Isolated plastic case recognized
according to UL 94-V0
Advantages
Easy installation
Small size and space saving
Only one design for wide current
ratings range
High immunity to external
interference.
Applications
DC motor drives
Switched Mode Power Supplies
(SMPS)
AC variable speed drives
Uninterruptible Power Supplies
(UPS)
Battery supplied applications
Power supplies for welding
applications
Application domain
Industrial

Summary of content (3 pages)