Datasheet

Electrical data
Primary nominal Primary current, Primary conductor Type RoHS since
current rms measuring range diameter x turns date code
I
PN
(A) I
PM
(A) (mm)
3 ± 9 0.6d x 20T HX 03-P planned
5 ± 15 0.8d x 12T HX 05-P 45341
10 ± 30 1.1d x 6T HX 10-P 45340
15 ± 45 1.4d x 4T HX 15-P 45352
20 ± 60 1.6d x 3T HX 20-P 45319
25 ± 75 1.6d x 2T HX 25-P 45351
50 ± 150 1.2 x 6.3 x 1T HX 50-P 45288
V
OUT
Output voltage (Analog) @ ± I
PN
, R
L
= 10 k, T
A
= 25°C ± 4 V
R
OUT
Output internal resistance < 50
R
L
Load resistance 10 k
V
C
Supply voltage (± 5 %)
1)
± 15 V
I
C
Current consumption < ± 15 mA
V
d
Rms voltage for AC isolation test, 50Hz, 1 min > 3 kV
V
e
Partial discharge extinction voltage rms @ 10 pC 1 kV
V
W
Impulse withstand voltage, 1.2/50 µs 6 kV
Accuracy-Dynamic performance data
X Accuracy @ I
PN
, T
A
= 25°C (excluding offset) < ± 1 % of I
PN
ε
L
Linearity error (0 .. ± I
PN
) < ± 1 % of I
PN
V
OE
Electrical offset voltage, T
A
= 25°C < ± 40 mV
V
OH
Hysteresis offset voltage @ I
P
= 0;
after an excursion of 1 x I
PN
< ± 15 mV
TCV
OE
Temperature coefficient of V
OE
< ± 1.5 mV/K
TCV
OUT
Temperature coefficient of V
OUT
(% of reading) ±
0.1 %/K
t
r
Response time to 90% of I
PN
step 3 µs
BW Frequency bandwidth (- 3 dB)
2)
50 kHz
General data
T
A
Ambient operating temperature - 25 .. + 85 °C
T
S
Ambient storage temperature - 25 .. + 85 °C
m Mass 8 g
dCp Creepage distance 5.5 mm
Isolation material group I
Standards EN50178: 1997
Current Transducer HX 03..50-P
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
I
PN
= 3 .. 50 A
Notes :
1)
Also operate at ±12V power supplies, measuring range reduced to ±2.5x I
PN
2)
Small signal only to avoid excessive heating of the magnetic cores
Features
Galvanic isolation between primary
and secondary circuit
Hall effect measuring principle
Isolation voltage 3000V
Low power consumption
Extended measuring range (3 x I
PN
)
Power supply from ±12V to ±15V
Isolated plastic case recognized
according to UL94-V0.
Advantages
Low insertion losses
Easy to mount with automatic
handling system
Small size and space saving
Only one design for wide current
ratings range
High immunity to external
interference.
Applications
Switched Mode Power Supplies
(SMPS)
AC variable speed drives
Uninterruptible Power Supplies
(UPS)
Electrical appliances
Battery supplied applications
DC motor drives
Application domain
Industrial
070313/11 www.lem.com
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/2