INSTALLATION INSTRUCTIONS ADAGIO™ Direct-Vent Gas Fireplaces P/N 850044M Rev. F 01/2011 MODELS This manual is one of a set of two supporting this product. Refer to P/N 875037M for Care and Operation Instructions. Ce manuel est disponible en francais, simplement en faire la demande. Numéro de la pièce 850044CF. MILLIVOLT: ADAGIO-MN ADAGIO-MP TM ELECTRONIC: ADAGIO-EN Portland US OTL Report No. 116-F-48-5 INSTALLER: Leave this manual with the appliance.
TABLE OF CONTENTS PACKAGING Packaging..........................................Page 2 Introduction.......................................Page 2 General Information...........................Page 2 Requirements for Commonwealth of Massachusetts.............................Page 4 New York City, New York (MEA).......... Page 4 Cold Climate Insulation........................ Page 5 Manufactured Home Requirements..... Page 5 Location Page....................................... 5 Vent Termination Clearances ...
WARNING Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier. WARNING Failure to comply with these installation instructions will result in an improperly installed and operating appliance, voiding its warranty. Any change to this appliance and/or its operating controls is dangerous.
Fuel # Minimum Maximum Natural Gas 5.0" WC (1.24 kPa) 10.5" WC (2.61 kPa) Propane 11.0" WC (2.74 kPa) 13.0" WC (3.23 kPa) Table 2 Manifold Gas Supply Pressure (all models) Fuel # Low High Natural Gas (Lo) 2.2" WC (.55 kPa) (Hi) 3.5" WC (.87 kPa) Propane (Lo) 6.3" WC (1.57 kPa) (Hi) 10.0" WC (2.49 kPa) Table 3 Test gauge connections are provided on the front of the millivolt and electronic gas control valve (identified IN for the inlet and OUT for the manifold side).
Cold Climate Insulation TOP VENT INSTALLATIONS This appliance may be installed in an aftermarket permanently located, manufactured home and must be installed in accordance with the manufacturer's instructions and the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, in the United States, or the Standard for Installation in Mobile Homes, CAN/CSA Z240 MH Series, in Canada. Cet appareil peut être installé cómme du matériel d'origine dans une maison préfabriquée (É.U.
VENT TERMINATION CLEARANCES These instructions should be used as a guideline and do not supersede local codes in any way. Install vent according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CSA-B149.1 in Canada. Vertical Vent Termination Clearances TERMINATION HEIGHTS FOR VENTS ABOVE FLAT OR SLOPED ROOFS Horizontal Overhang Terminate multiple vent terminations according to the installation codes listed above.
Exterior HORIZONTAL Vent TERMINATION Clearance Requirements NOTE: Local Codes Or Regulations May Require Different Clearances. * See Item D in the Text Below. P N NOTE: Location Of The Vent Termination Must Not Interfere With Access To The Electrical Service. Inside Corner Detail Exterior Wall *18” Horizontal Termination G V 6” N O Q V V Ventilated Soffit A Inside Corner in U.S. � A == 9” 12” in Canada Detail D H 3 ft.
MINIMUM CLEARANCES TO COMBUSTIBLES Appliance And Vent Clearances The appliance is approved with zero clearance to combustible materials on all sides (as detailed in Table 5), with the following exception: When the unit is installed with one side flush with a wall, the wall on the other side of the unit must not extend beyond the front edge of the unit. In addition, when the unit is recessed, the side walls surrounding the unit must not extend beyond the front edge of the unit (see Figure 3).
WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury. AVERTISSEMENT Risque de dommages ou de blessures si les pièces ne sont pas installées conformément à ces schémas et ou si des pièces autres que celles spécifiquement approuvées avec cet appareil sont utilisées.
fireplace AND FRAMING specifications Framing Dimensions - All Models Framing With Platform Inches (millimeters) A * B C D in. 22-1/8 40-1/4 15-3/4 44-1/8 mm 562 1022 400 1121 10¹⁄₂ Framing should be constructed of 2x4 or larger lumber D shown here is not dimensioned to the vertical center of the horizontal framing. This is to allow for the required 4" clearance above the vent and the 1" required clearance below the vent.
FACADE specifications Arch Facades** Black and Brushed Nickel Finishes Cat. No. Model H5773 ADAGIO-AG Arch Black H5774 ADAGIO-PF Arch Br. Nickel Facade (Required) * (arched style shown) 1/2” (13mm) 1-1/2” (38mm) Description ** A filigree inset kit is also required (sold separately). See Care and Operation Manual for ordering information. 20-1/4” (514) 38-1/2” (978) 1/2” (13) 14-13/16” (376) 26-3/4” (680) Gated Facades Copper and Iron Gates Cat. No.
Corner Framing Dimensions - All Models Top Vent With Horizontal Termination In A Corner A B C D E in. 22-1/8 41-5/8 29-1/2 10 20-7/8 mm 562 1057 749 254 530 D 7 (178) uWhen installing in a corner configuration, one of the rear stand-offs will need to be removed. � C E A Figure 14 - Corner Framing with Square Termination (SV4.5HT-2) B Back wall of chase/enclosure (including any finishing materials) Step 2.
Step 3. Install the Vent System General Information These instructions should be used as a guideline and do not supersede local codes in any way. Install vent according to local codes, these instructions, the current National Fuel Gas Code (ANSI-Z223.1) in the USA or the current standards of CAN/CSA-B149.1 in Canada. Ensure clearances are in accordance with local installation codes and the requirements of the gas supplier. Use only approved venting components. See Approved Vent Components on Page 2.
Vertical Termination Systems (Roof) See Figures 16, and 24 through 26 on Pages 14 and 17 and their associated Vertical Vent Tables which illustrate the various vertical venting configurations that are possible for use with these appliances. Secure Vent™ pipe applications are shown in these figures; Secure Flex™pipe may also be used.
Vertical (Offset) Installation Analyze the vent routing and determine the quantities of vent sections and number of elbows required. Refer to Vertical Vent Figures and Tables on Page 17 to select the type of vertical installation desired. Vent sections are available in net lengths of 4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" (876 mm) and 46-1/2" (1181 mm). Refer to the Vent Section Length Chart on Page 14 for an aid in selecting length combinations.
One method of support is by utilizing field provided support straps (conventional plumber's tape). Secure the plumber's tape to the framing members with nails or screws. Loop the tape around the vent, securing the ends of the tape to the framing. If desired, sheet metal screws #6 x 1/2" length may be used to secure the support straps to the vent pipe. See Figure 19. F. Change vent direction to horizontal/inclined run - At transition from or to a horizontal/inclined run, install the SV4.5E45 and SV4.
VERTICAL VENT FIGURES/TABLES Notes: • Secure Vent™ (rigid vent pipe) is shown in the Figures; Secure Flex™ (flexible vent pipe) may also be used. • It is very important that the horizontal/inclined run be maintained in a straight (no dips) and recommended to be in a slightly elevated plane, in a direction away from the fireplace of 1/4" rise per foot (20 mm per meter) which is ideal, though rise per foot run ratios that are smaller are acceptable all the way down to at or near level. • SV4.
Horizontal (Outside Wall) Termination System See Figures 27, and Figures 30 to 33 on Pages 18, 20 and 21 and their associated Horizontal Vent Table which illustrate the various horizontal venting configurations that are possible for use with these appliances. Secure Vent™ pipe applications are shown in these figures; Secure Flex™ pipe may also be used.
J. Assemble vent run to exterior wall - If not previously measured, locate the center of the vent at the exterior wall. Prepare an opening as described in Step B. Assemble the vent system to point where the terminus of the last section is located relative to the exterior surface to which the termination is to be attached as shown in Figure 29 and Table 8. If the terminus of the last section is not within this distance, use the telescopic vent section SV4.5LA, as the last vent section.
See Table 8 as an aid in venting component selection for a particular range of exterior wall thicknesses. Venting Components Required for Various Exterior Wall Thicknesses, when using Square Termination Kit (SV4.5HT-2) Vent Components Required Termination Kit Only Exterior Wall Thickness - inches (mm) 6 to 9-1/4 (152 to 235) Termination Kit and 6 In. Vent Section (SV4.5L6) 10-3/4 to 14 (273 to 356) Termination Kit and 12 in. Vent Section (SV4.
HORIZONTAL VENT FIGURES / TABLES (CONTINUED) Table E �Wall Firestop/Spacer H H1 V (meter) (SV4.5HF) use Firestop/Spacer SF4.5HF. �Ceiling Firestop/Spacer (SV4.5VF) Square termination (SV4.5HT-2) shown. feet (meter) 3 (0.914) 5 (1.524) 1 (0.305) 10 (3.048) 2 (0.610) 15 (4.572) 3 (0.914) (6.096) 4 (1.219) Elbow Only V + H + H1 = 40 feet (12.2 m) Max. H + H1 = 20 feet (6.096 m) Max.
Vertical or Horizontal Venting Using Secure Flex™ Kits and Components Secure Flex™ venting kits and components may be used in any venting application in place of rigid Secure Vent™ (SV4.5) direct-vent components. All restrictions, clearances and allowances that pertain to the rigid piping apply to the flexible venting. Secure Flex kits may not be modified; also, under no circumstances may separate sections of flex pipe be joined together.
Refer to Section A for millivolt appliances and Section B for electronic appliances. The gas valve is set in place and pre-wired at the factory on both models. Step 4. Field Wiring CAUTION Ground supply lead must be connected to the wire attached to the green ground screw located on the outlet box. See Figure 38. Failure to do so will result in a potential safety hazard.
Ground - Green Neutral - White 120 VAC - Black BLOWER CONTROL CIRCUIT WIRING 120V, 60HZ, 1PH * Wall-mounted ON/ OFF Blower Switch or Variable Speed Control Switch. Junction Box Hot Side of Receptacle Red Black Green White Tab Broken Blower Tab Intact The millivolt and electronic control valve has a 3/8" (10 mm) NPT thread gas supply inlet. Bring the shutoff valve on the end of the flex-line over to the hard pipe and tighten with wrenches from above through the firebox opening.
TEST ALL CONNECTIONS FOR GAS LEAKS (FACTORY AND FIELD): WARNING Never use an open flame to check for leaks. Turn on gas supply and test for gas leaks using a gas leak test solution (also referred to as bubble leak solution). Note: Using a soapy water solution is an effective leak test solution but it is not recommended, because the soap residue that is left on the pipes/fittings can result in corrosion over time. A.
Step 8. Installing the Logs AND Glowing Embers LOG SET Catalog Number H1237 A FIREBOX LINER KIT MUST BE INSTALLED BEFORE INSTALLING LOGS. THIS APPLIANCE IS NOT APPROVED FOR OPERATION WITHOUT A FIREBOX LINER KIT INSTALLED (SOLD SEPARATELY). SEE PAGE 15 IN CARE AND OPERATION MANUAL FOR ORDERING INFORMATION. INSTALL LINER KIT AND LOG SUPPORT BRACKET PER INSTRUCTIONS PROVIDED IN KIT. * Item Locate log set carton and plastic bag of glowing embers.
1. Place the rear log (A) as shown in Figure 44. Position the 2 holes on the bottom of the log over the corresponding locating pins (#1 & #2) and against the log support bracket. See Figures 43 and 44 for pin and rear bracket locations. 4. Place the right front log (E) as shown in Figure 47. Position the hole on the bottom of log E over pins #4 and # 5. A 1 2 3 4 E 5 Figure 44 - Install Rear Log (A) Figure 47 - Install Right Front Log (E) 2. Place the left middle log (B) as shown in Figure 45.
Step 9.INSTALLATION AND REMOVAL OF GLASS DOOR WARNING • Do not attempt to substitute the materials used on these doors, or replace cracked or broken glass. • Handle this glass with extreme care! Glass is susceptible to damage – Do not scratch or handle roughly while reinstalling the glass door frame. • The glass door(s) of this appliance must only be replaced as a complete unit as provided by the manufacturer. Do not attempt to replace broken, cracked or chipped glass separately.
Step 10. Burner Adjustments Flame Appearance and sooting Proper flame appearance is a flame which is blue at the base and becomes yellowish-orange in the body of the flame. When the appliance is first lit, the entire flame may be blue and will gradually turn yellowish-orange during the first 15 minutes of operation. After 15 minutes of operation, if the flame is blue, or if the flame is orange with evidence of sooting (black tip), the air shutter opening may need to be adjusted.
Finishing Requirements - Wall Details Complete finished interior wall. To install the appliance facing flush with the finished wall, position framework to accommodate the thickness of the finished wall (Figure 54). This Area Must Remain Clear of Combustible Materials Drywall Header (2x4) 4" Min � (102 mm)* 1" Min. (25 mm)* Figure 53 - Burner Flame Appearance IMPORTANT NOTE: Place the header vertical as shown to maintain proper clearance from the vent system to combustibles.
Step 11. ATTACHING SAFETY IN OPERATION WARNINGS It is the installer's responsibility to ensure these warnings are properly affixed during installation. These warning labels are a critical step in informing consumers of safe operation of this appliance.
Installation Accessories Listed Secure Flex™ Components Listed Secure Vent™ Components Vent Sections Cat. No. Model Description H1968 SV4.5HT-2 Horizontal Square Termination With Firestop / spacer (H2246) & Adaptor (74L61) H2152 SV4.5CGV-1 77L70 SV4.5L6 6 Inch (152 mm) 77L71 SV4.5L12 12 Inch (305 mm) 77L72 SV4.5L24 24 Inch (610 mm) 77L73 SV4.5L36 36 Inch (914 mm) 77L74 SV4.5L48 48 Inch (1219 mm) 77L75 SV4.5LA Telescopic Section (1-1/2" to 7-1/2" effective length) 77L76 SV4.
Installation Instructions Gas Conversion Kits WARNING This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instruction is not followed exactly, a fire, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life.
SIT Millivolt Gas Valve Shown SIT Millivolt Pilot Assembly Shown Burner Orifice Sizes Elevation 0-4500 feet ( 0-1372 meters) Model Pressure Regulator Pilot Orifice Thermopile (on millivolt pilot assemblies only) Remove These Components Nat.Gas Propane Series drill size (inches) drill size (inches) Adagio-MN .067" (#51) ------------- Adagio-MP ------------- .042" (#58) Adagio-EN .067" (#51) ------------- Adagio-EP if field converted ------------- .
NOTES 35
Lennox Hearth Products reserves the right to make changes at any time, without notice, in design, materials, specifications, prices and also to discontinue colors, styles and products. Consult your local distributor for fireplace code information. Printed in U.S.A. © 2007 Lennox Hearth Products P/N 850044M REV.