Water Heater User Manual

Page 15
CBWMV SERIES
Table 7
CBWMV−36C−090 Blower Performance
0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range ; Factory Settings: Heating Speed − 4, Cooling
Speed − 3, Speed Adjust − NORM; Applications with single sided inlets will reduce CFM by approximately 5%.
ADJUST"
BDC3 Jumper Speed Positions
ADJUST"
Jumper
1st Stage COOL" Speed
J
umper
Sett
in
g
1 2 3 4
Setting
cfm L/s cfm L/s cfm L/s cfm L/s
+ 620 290 770 365 930 440 1010 475
NORM 570 270 700 330 830 390 910 430
520 245 630 295 760 360 810 380
ADJUST"
HEAT" Speed 2nd Stage COOL" Speed
ADJUST
Jumper
S
1 2 3 4 1 2 3 4
p
Setting
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+ 820 385 1000 470 1180 555 1340 630 890 420 1130 535 1340 630 1450 685
NORM 760 360 900 425 1070 505 1220 575 800 380 1020 480 1220 575 1310 620
675 320 810 380 950 450 1100 520 720 340 900 425 1100 520 1180 555
The effect of static pressure and filter resistance is included in air volumes shown.
1st stage COOL is approximately 70% of the same 2nd stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same 2nd stage COOL speed position.
Lennox Harmony zone control applications − Minimum blower speed is 400 cfm. Max cfm is the same as 2nd stage cool position.
Table 8
CBWMV−60C−100 Blower Performance
0 through 0.80 in. w.g. (0 Through 200 Pa) External Static Pressure Range ; Factory Settings: Heating Speed − 4, Cooling
Speed − 3, Speed Adjust − NORM; Applications with single sided inlets will reduce CFM by approximately 5%.
ADJUST"
BDC3 Jumper Speed Positions
ADJUST"
Jumper
1st Stage COOL" Speed
J
umper
Setting
1 2 3 4
Setting
cfm L/s cfm L/s cfm L/s cfm L/s
+ 1110 525 1250 590 1380 650 1530 720
NORM 1000 470 1130 535 1250 590 1380 650
930 440 1040 490 1130 535 1260 595
ADJUST"
HEAT" Speed 2nd Stage COOL" Speed
ADJUST
Jumper
1 2 3 4 1 2 3 4
p
Setting
cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s cfm L/s
+ 1500 710 1700 800 1880 885 2100 990 1540 725 1760 830 1970 930 2200 1040
NORM 1370 645 1540 725 1720 810 1920 905 1400 660 1600 755 1800 850 1980 935
1250 590 1380 650 1540 725 1720 810 1270 600 1420 670 1600 755 1780 840
The effect of static pressure and filter resistance is included in air volumes shown.
1st stage COOL is approximately 70% of the same 2nd stage COOL speed position.
Continuous Fan Only speed is approximately 38% of the same 2nd stage COOL speed position.
Lennox Harmony zone control applications − Minimum blower speed is 600 cfm. Max cfm is the same as 2nd stage cool position.