Product Overview
Table Of Contents
- ICOMFORT® S30 THERMOSTAT
- BASIC INFOMATION
 - INSTALLER SETTINGS
 - USER SETTINGS
- ACCOUNT SCREEN
 - ADVANCED SETTINGS (INSTALLER SETTINGS)
 - AWAY SCREEN
 - AWAY SETTINGS SCREEN
 - COOL MENU SCREEN
 - DISPLAY SCREEN
 - EDIT SCHEDULES SCREEN
 - FAN SCREEN
 - FEELS LIKE SCREEN
 - GENERAL SCREEN
 - HEAT/COOL SCREEN
 - HEAT MENU SCREEN
 - HOME INFO SCREEN
 - HOME SCREEN (Thermostat ON)
 - HUMIDITY SCREEN (Humidity Control)
 - IHARMONY ZONING SCREEN (if equipped)
 - MENU SCREEN
 - MODES/SCHEDULES SCREEN
 - NAME SCREEN
 - NOTIFICATIONS (REMINDERS) SCREEN
 - PUREAIR™ S PERFORMANCE SCREEN
 - SCHEDULE HOLD SCREEN
 - SCHEDULES SCREEN
 - SETTINGS SCREEN
 - VENTILATION SCREEN (Fresh Air Damper/HRV/ERV)
 - WEATHER FORECAST SCREEN
 - WI-FI SCREEN
 - ZONING SCREEN
 
 
 - REVISIONS
 
iComfort
®
 S30 Ultra Smart Thermostat / Page 32
INSTALLER SETTINGS
EQUIPMENT (continued)
Air Handler
(About)
•  Unit Code
•  Language Support
•  Equipment Type name
•  Unit Model Number
•  Unit Serial Number
•  Unit Nominal Capacity
•  Number of Heating Stages
•  Heating Capacity by Stage
•  Indoor Blower CFM Range
•  Control Software Revision
•  Control Model Number
•  Control Serial Number
•  Control Hardware Revision
•  Discharge Air Temp Sensor
•  Outdoor Air Temp Sensor
•  Protocol Revision Number
•  Device Product Level
•  Factory Installed Transformer
•  24VAC Average Power Consumption
•  24VAC Peak Power Consumption
•  Line Voltage Average Power Consumption
•  Line Voltage Peak Power Consumption
•  Compatible Devices List
•  Application Code Memory Size
•  Microcontroller Part Number
(Adjust Settings)
•  Equipment Name (Keyboard tool)
•  Electric Heating Airow
•  Low Cooling Airow (XC21, XP21)
•  High Cooling Airow
•  Airow Prole - Cooling (default is 1)
•  No Delays
•  On (No delays); Off (45 sec. delay)
•  On (82% for 7.5 min.); Off (No delays)
•   On (50% for 30 sec., 82% for 7.5 min.); Off (50% for 30 
sec.)
XC21, XP21
•  Low HP Airow (XP21)
•  High HP Airow
•   Continuous Indoor Blower Airow (450 to 2150 cfm, 
default is 800 cfm)
•  Humidication Airow (Humidier)
All airow parameters are determined by settings in 
communicating equipment and are dependent on the 
capacity of the unit. 
•   Dehumidication Airow (Dehumidier) 
(60 to 80%, default is 70%)
Dehumidication Airow is 60 to 80% reduction of the 
High Cooling Airow parameter.
(Adjust Settings)
•  Delay Settings
•   Heating Indoor Blower OFF 
(0 to 10 sec., default is 10 sec.)
•   Heating Indoor Blower ON 
(0 to 5 sec., default is 0 sec.)
•   Cooling Indoor Blower OFF 
(0 to 30 sec., default is 0 sec.)
•   Cooling Indoor Blower ON 
(0 to 10 sec., default is 2 sec.)
•   HP Indoor Blower OFF 
(0 to 60 sec., default is 45 sec.)
•   HP Indoor Blower ON 
(0 to 30 sec., default is 0 sec.)
•  Reset Air Handler (factory default settings)
Zoning Control
(About)
•  Unit Code
•  Language Support
•  Equipment Type name
•  Control Software Revision
•  Control Model Number
•  Control Serial Number
•  Control Hardware Revision
•  Protocol Revision Number
•  Device Product Level
•  24VAC Average Power Consumption
•  24VAC Peak Power Consumption
•  Compatible Devices List
•  Application Code Memory Size
•  Microcontroller Part Number
•  Maximum Number of Zones
•  Supported Damper Types
(Adjust Settings)
•  Equipment Name (Keyboard tool)
•   Zone 1 Temperature Reading Calibration (–5 to 5°F, 
default is 0°F)
•   Zone 2 Temperature Reading Calibration (–5 to 5°F, 
default is 0°F)
•   Zone 3 Temperature Reading Calibration (–5 to 5°F, 
default is 0°F)
•   Zone 3 Temperature Reading Calibration (–5 to 5°F, 
default is 0°F)
•  Reset Zoning Control (factory default settings)
FEATURES