User Guide
506052−01 11/09
Page 26
Parameter Name: IncrementParameter Value SettingDefault
1st Stage Differential 0.5ºF 0.5 to 3ºF .5ºF
2nd Stage Differential 1.5ºF 0.5 to 8ºF .5ºF
3rd Stage Differential 2.0ºF 0.5 to 8ºF .5ºF
4th Stage Differential 2.5ºF 0.5 to 8ºF .5ºF
5th Stage Differential 3.0ºF 0.5 to 8ºF .5ºF
6th Stage Differential 3.5ºF 0.5 to 8ºF .5ºF
Stage Delay Timers Enabled Enabled, Disabled
2nd Stage Delay 20 Minutes 5 to 120 Minutes 5 Min
3rd Stage Delay 20 Minutes 5 to 120 Minutes 5 Min
4th Stage Delay 20 Minutes 5 to 120 Minutes 5 Min
5thStage Delay 20 Minutes 5 to 120 Minutes 5 Min
6th Stage Delay 20 Minutes 5 to 120 Minutes 5 Min
Locked in 2nd Stage HP by Outdoor Temp Off Off, 40F (4C), 45F (7C), 50F (10C), 55F (13C),
Balance Point Control Disabled Enabled, Disabled
Defrost Target Discharge Temp 55ºF 50 to 60ºF 1ºF
Dehumidification Control Mode Display Only Display Only, Basic, Precision
Humidification Control Mode Display Only Display Only, Basic, Precision, Dew Point Control
Autochangeover Humidification Deadband 5% 5 to 10% 1ºF
Max Humidification Setpoint 45% 15 to 45% 1ºF
Max Dehumidification Setpoint 40% 40 to 60% 1ºF
OK/Humid Boundary 50% 45 to 60% 1ºF
table continued on next page










